2019-05-20 14:07:38 | ***CORRECTIONS*** |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 2ND BUILDING PLAN REVIEW DENIED: |
| |
| (THE COMMENTS FROM ITEM #1 OF THE 1ST REVIEW, NOTED |
| BELOW, STILL HAVE NOT BEEN CORRECTED.) |
| 1. THE SUBMITTED SHEET A?1 DOES NOT INDICATE WHO THE |
| DESIGNER OF THE PLAN IS? |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| ONE SHEET. |
| |
| (THE COMMENTS FROM ITEM #2 OF THE 1ST REVIEW, NOTED |
| BELOW, STILL HAVE NOT BEEN CORRECTED.) |
| 2. THE SUBMITTED SHEET A?1 DOES NOT COMPLY WITH RECORD |
| RETENTION STANDARDS FOR SCANNING. 107.2.1.3 QUALITY OF |
| BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A |
| MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| |
| (THE COMMENTS FROM ITEM #3 OF THE 1ST REVIEW, NOTED |
| BELOW, ONLY HAVE CORRECTIONS IN ONE DETAILED SECTION OF |
| SHEET A-1. THE OTHER DETAILED SECTIONS OF SHEET A-1 |
| NEED TO BE CORRECTED.) |
| 3. SHEET A?1 DETAIL # 1 CABINET ELEVATION SHOWS A |
| MICROWAVE ON A SHELF WITH THE BOTTOM OF THE MICROWAVE |
| AT A HEIGHT OF 4 FOOT 10 INCHES OR AT 58 INCHES ABOVE |
| FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE 2017 |
| FBC?ACCESSIBILITY CODE SECTIONS: 308 REACH RANGES. |
| 308.2 FORWARD REACH./ 308.2.1 |
| UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| MAXIMUM. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| |
| |