2019-01-25 15:44:01 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; WPB FBC 107.2.1 |
| 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| 3. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR |
| ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, |
| 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| 4. PROVIDE DISTANCE OF LIGHT FIXTRES TO POOL WATER TO |
| CONFIRM CODE COMPLIANCE. ALSO PROVIDE SPEC SHEETS FOR |
| LIGHT FIXTURE WHICH INCLUDE TYPE OF FIXTURE AND |
| VOLTAGE. WPB FBC 107.2.1; NEC 680.22 |
| 5. ALL EXTERIOR RECEPTACLES REQUIRE GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.3 |
| 6. WHAT SIZE BREAKER WILL 6-3 ROMEX BE ATTACHED TO? |
| THIS SIZE ROMEX IS GOOD FOR 50 AMPS. NEC 334.80; FBC RE |
| E3705.4.4 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |