Plan Review Notes
Plan Review Notes For Permit 19010903
Permit Number 19010903
Review Stop G
Sequence Number 2
Notes
Date Text
2019-02-19 04:47:451) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THE PERMIT
 APPLICATION FOLDER SHOWING TWO DIFFERENT TOTAL BTU
 LOADS FOR THE GAS SYSTEM. ONE GAS DRAWING SHOWS A TOTAL
 BTU LOAD OF 215,000 BTU'S AND THE OTHER DRAWING SHOWS A
 TOTAL BTU LOAD OF 245,000 BTU'S. CLARIFY. REMOVE OLD
 DRAWINGS FROM THE PERMIT APPLICATION PACKAGE.WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) IF THE TOTAL BTU LOAD IS 245,000 THEN THE 1 INCH
 LINE FROM THE METER IS UNDERSIZED PER SIZING TABLE
 402.4 (2). CLARIFY .
 3) THE 1/2 INCH LINE TO THE STOVE IS UNDERSIZED. THE
 LINE SHALL BE A MINIMUM OF 3/4 INCH PER TABLE 402.4 (2)
 BASED ON THE LENGTH OF 80 FEET.
 4) GAS PIPING INSTALLED ACROSS ROOF SURFACES SHALL BE
 ELEVATED NO LESS THAN 3 1/2 INCHES ABOVE THE ROOF
 SURFACE. 2017 FBC-FUEL GAS SEC.404.9. PLACE A NOTE ON
 THE PLANS REFERENCING THIS CODE SECTION.
 5) THE MINIMUM SIZE PIPE TO THE TANKLESS WATER HEATER
 SHALL BE 1 INCH PER TABLE 402.4(2). A 3/4 INCH METALLIC
 PIPE CAN ONLY CARRY 117,000 BTU'S UNDER THE 80 FEET ROW
 IN THE GAS TABLE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  