Plan Review Notes
Plan Review Notes For Permit 19010781
Permit Number 19010781
Review Stop P
Sequence Number 1
Notes
Date Text
2019-01-24 06:44:091) SUBMIT A CODE COMPLIANT SANITARY RISER DIAGRAM FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.3.5.3.
 2) SHOW ALL PIPE SIZES ON THE REQUESTED SANITARY
 RISER.WPB AMEND. TO FBC SEC. 107.2.1.
 3) WHAT IS DISCHARGING INTO THE OUTSIDE DRAIN?
 RAINWATER CANNOT DISCHARGE TO THE SANITARY SYSTEM PER
 CITY ORDINANCE.
 4) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING
 OF THE DOWELS ON CENTER. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR
 BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR FINAL INSPECTION.
 5) A CLEANOUT BROUGHT TO GRADE SHALL BE INSTALLED AT
 THE CONNECTION AT THE CITY LATERAL.
  
 A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED DUE TO
 THE LACK OF REQUIRED INFORMATION ON THE PLAN.
  
  