2019-01-28 12:30:05 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19010744 |
| ADD: 1701S. FLAGLER DR. APT.: 303 |
| CONT: AOA CONSTRUCTION LLC |
| TEL: 561-660-3504 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JAN. 28/ 2019 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THE SUBMITTED PERMIT APPLICATION WAS |
| SUBMITTED ELECTRONICALLY, A PAPER ORIGINAL WILL BE |
| REQUIRED BEFORE PERMIT ISSUANCE WITH BOTH THE OWNER AND |
| CONTRACTOR SIGNATURES AND NOTARIZED. |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, SECTION 105.3 APPLICATION FOR PERMIT. |
| |
| 2) PLEASE NOTE THE WINDLOAD CHART SUBMITTED FROM |
| ENGINEERING EXPRESS, FRANK BENNARDO P. E. IS A PAPER |
| COPY SCANNED INTO THE COMPUTER, THE DIGITAL SEAL INFO |
| IS NOT AN ORIGINAL ELECTRONIC SIGNATURE AND SEAL, IT |
| CANNOT BE OPENED AND VERIFIED. |
| 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| REPORTS OR OTHER DOCUMENTS. |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| 3) THE SUBMITTED DOCUMENT ILLUSTRATION CHAUDRIC DOES |
| NOT STATE WHO THE AUTHOR IS OF THIS DOCUMENT. PLEASE |
| SHOW COMPLIANCE WITH 2017 FLORIDA BUILDING CODE W 2017 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.2 |
| CERTIFICATIONS BY CONTRACTORS AUTHORIZED UNDER THE |
| PROVISIONS OF SECTION 489.115 FLORIDA STATUTES, SHALL |
| BE CONSIDERED EQUIVALENT TO SEALED PLANS AND |
| SPECIFICATIONS BY A PERSON LICENSED UNDER CHAPTER 471, |
| FLORIDA STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY |
| LOCAL ENFORCEMENT AGENCIES FOR PLANS REVIEW FOR |
| PERMITTING PURPOSES RELATING TO COMPLIANCE WITH THE |
| WIND-RESISTANCE PROVISIONS OF THE CODE OR ALTERNATE |
| METHODOLOGIES APPROVED BY THE FLORIDA BUILDING |
| COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. LOCAL |
| ENFORCEMENT AGENCIES MAY RELY UPON SUCH CERTIFICATION |
| BY CONTRACTORS THAT THE PLANS AND SPECIFICATIONS |
| SUBMITTED CONFORM TO THE REQUIREMENTS OF THE CODE FOR |
| WIND RESISTANCE. UPON GOOD CAUSE SHOWN, LOCAL |
| GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT OR |
| REJECT PLANS SEALED BY PERSONS LICENSED UNDER CHAPTERS |
| 471,481 OR 489, FLORIDA STATUTES. |
| |
| 4) THE SECOND ISSUE WITH THE SUBMITTED DOCUMENT |
| ILLUSTRATION CHAUDRIC IS THAT IT DOES NOT PROVIDE WHERE |
| THIS UNIT IS COMPARED WITH THE OVERALL CONFIGURATION OF |
| THE BUILDING IF THE UNIT IS TO BE CONSIDERED AS AN |
| INTERIOR ZONE (4) OR AN END ZONE (5). 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 5) THE WINDOW AND DOOR SCHEDULE INDICATES THE OPENING |
| SIZE OF THE OVERALL OPENING SIZE BUT NOT THE PANEL |
| SIZE, EXAMPLE THE SUBMITTED NOA EGS INTERNATIONAL |
| ALUMINUM SLIDING DOORS L.M.I. 17-1218.22 ON PAGE 5 OF |
| 11 NO ONE HAS IDENTIFIED THE PANEL WIDTH, HEIGHT, TYPE |
| OF GLAZING, IF REINFORCEMENT IS REQUIRED OR NOT, NOR |
| THE SILL HEIGHT WHICH LIMITS THE ALLOWABLE PSF. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 6) THE SUBMITTED MIAMI-DADE NOA 17-0731.06 HAS THE SAME |
| PROBLEM. NO ONE HAS IDENTIFIED THE OVERALL WINDOW |
| HEIGHT, WIDTH, AND TYPE OF GLASS NOR THE ASSOCIATED |
| PRESSURES. NOTE THIS REPORT DOES REQUIRE A SEPARATE |
| MIAMI-DADE NOA FOR MULTIPLE USE OF WINDOWS WITHIN THE |
| SAME OPENING. PAGE 7 OF 9 IN THE REPORT INDICATES THE |
| TYPE OF FASTENERS, BUCKS AND SPACING, AGAIN NO ONE HAS |
| TAKEN RESPONSIBILITY FOR IDENTIFYING THE TYPE OF |
| FASTENER. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 7) THE SUBMITTED MIAMI-DADE NOA 17-0717.02 FOR MULLIONS |
| IS A 22 PAGE REPORT. AGAIN AS IN THE LAST 2 COMMENTS, |
| NO ONE HAS TAKEN THE RESPONSIBILITY FOR THE TRIBUTARY |
| AREA THE MULLION IS GOING TO CARRY, THE PRESSURES, |
| MULLION CONFIGURATION, TYPE OF ANCHORS, IF THE MULLION |
| IS TO REQUIRE REINFORCEMENT OR NOT. . 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 8) PLEASE NOTE THAT WHEN THIS BUILDING WAS BUILT IT WAS |
| COMMON TO INSTALL BEVELED WINDOW AND DOOR BUCKS. THE |
| CODE DOES NOT ALLOW THAT ANYMORE. PLEASE PROVIDE A BUCK |
| DETAIL AND ANCHORING SCHEDULE FOR BOTH THE WINDOWS AND |
| SLIDING GLASS DOORS. SHOW COMPLIANCE WITH THE 2017 |
| FBC-B SECTION: |
| 1703.4.1 RESEARCH AND INVESTIGATION. SUFFICIENT |
| TECHNICAL DATA SHALL BE SUBMITTED TO THE BUILDING |
| OFFICIAL TO SUBSTANTIATE THE PROPOSED USE OF ANY |
| PRODUCT, MATERIAL OR ASSEMBLY. IF IT IS DETERMINED THAT |
| THE EVIDENCE SUBMITTED IS SATISFACTORY PROOF OF |
| PERFORMANCE FOR THE USE INTENDED, THE BUILDING OFFICIAL |
| SHALL APPROVE THE USE OF THE PRODUCT, MATERIAL OR |
| ASSEMBLY SUBJECT TO THE REQUIREMENTS OF THIS CODE. THE |
| COSTS, REPORTS AND INVESTIGATIONS REQUIRED UNDER THESE |
| PROVISIONS SHALL BE PAID BY THE OWNER OR THE OWNER?S |
| AUTHORIZED AGENT. |
| |
| 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |