2019-03-13 08:51:52PLUMBING APPROVED WITH PROVISO:
  
 1) ANY AND ALL WORK COVERED UP SHALL BE OPENED FOR
 INSPECTION AND INCLUDES BUT LIMITED TO. SHOWER WET
 WALLS, SHOWER PAN, CLOTHS WASHER AND ANY OTHER AREA
 THAT NEW PIPING IS IN. FBC 110.3
  
 2 ANY AND ALL THROUGH FLOOR PENETRATIONS SHALL BE
 SEALED WITH MATERIALS COMPLYING WITH THE FBC CHAPTER 7
 FIRE AND SMOKE AND FBC ENERGY CODE IN FULL. RATED
 ASSEMBLY FOR SAID PENETRATIONS SHALL BE INCORPORATED
 INTO THE PLANS BY A APPROVED REVISION PRIOR TO THE 1ST
 INSPECTION. FBC 107.2.1. DOCUMENTS SHALL BE SIGNED AND
 SEAL BY DESIGN PROFESSIONAL OF RECORD. FBC 107.1
  
 3) PLUMBING ISOMETRIC HAS BEEN RED LINE TO MEET FBC
 PLUMBING CODE.
  
 4) HAMMER ARRESTORS SHALL BE USED AT ALL QUICK CLOSING
 VALVES. FBC-P 604.9
  
 5) SHOWER PAN SHALL BE PRE-PITCH 1/4" PER FOOT. FBC RES
 P2709.3
  
 6) SHOWER AND TUB VALVES SHALL BE PRESSURE BALANCED,
 THERMOSTATIC AND A HIGH LIMIT OF 120F
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH