2019-02-05 12:48:46 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19010730 |
| 2/5/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET MEP-1: THERE ARE GENERAL NOTES ON THE PLAN FOR |
| MECHANICAL BUT NO SPECIFIC PLAN OR NOTES FOR THE |
| PROPOSED ALTERATION. PLEASE PROVIDE A COMPLETE SCOPE OF |
| WORK OUTLINE AND MECHANICAL PLAN THAT SHOWS ALL |
| ALTERATIONS TO THE EXISTING SYSTEMS INCLUDING A DUCT |
| LAYOUT PLAN, AC EQUIPMENT SCHEDULE, AND THE RELOCATED |
| DRYER EXHAUST RUN. PLEASE INCLUDE AN AC CHANGEOUT FORM |
| IF THE SYSTEM IS BEING REPLACED- SECTION 107.2.1 WPB. |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER, |
| THE RANGE, AND MICROWAVE- SECTIONS 504.1, AND 505.1 FBC |
| M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |