Plan Review Notes
Plan Review Notes For Permit 19010587
Permit Number 19010587
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-12 15:24:29BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE INFILLS ARE SUBJECT TO WIND LOADS, AN ENGINEER
 MUST DESIGN THE INFILL OPENINGS. FS 471.003.2.A.C.(I),
  
 2. PLEASE SUBMITT AN ENGINEERED DESIGN PER FBC 2104;
 TMS602/ACI 530