2019-01-16 07:29:28 | 01/15/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| |
| 1. SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (TO |
| VERIFY COMPLIANCE WITH WATER HEATERS, DRYER AND RANGE), |
| GAS 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| 2. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| ON THE APPLICATION IN THE DESCRIPTION OF WORK. WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS |
| 3. THE TANKLESS WATER HEATER AND THE LOCATION AND |
| DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4. A SUB PLUMBING AND ELECTRICAL FOR OUTLET MAY BE |
| REQUIRED FOR THE SOURCE OF IGNITION, WPB AMENDMENTS TO |
| THE FBC SEC. 105.1. |
| 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS RES. |
| SECS. G2426 THRU G2429.1 |
| 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| GAS RES. SEC. G2413.2 AND G2404.3. |
| 8. SHOW SHUTOFF VALVE AND DRIP LEGS ON GAS ISOMERIC, |
| 2017 FBC FUEL GAS RES. SEC. 409.5, APPLIANCE CONNECTION |
| 2017 FBC FUEL GAS RES. SEC. 404.15, 411. |
| 9. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THROUGH |
| THE EXTERIOR WILL BE PROTECTED. WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1. |
| 10. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING |
| PERMITS VALUATIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |