Plan Review Notes
Plan Review Notes For Permit 19010326
Permit Number 19010326
Review Stop M
Sequence Number 1
Notes
Date Text
2019-02-28 12:43:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010326
 2/28/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE EQUIPMENT SCHEDULES FOR THE EXISTING RTU'S
 INDICATING MAKES AND MODELS, COOLING AND HEATING
 CAPACITIES, AND TOTAL SUPPLY CFMS- SECTION 107.2.1 WPB,
 AND SECTIONS 304.1 AND 603 FBC M.
  
 2) SHEET M1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYUSTEMS OF THE RTU'S- SECTION 606.2.1 FBC M.
  
 3) LS1.1 & M1.1: FIRE DAMPERS ARE REQUIRED AT THE
 PENETRATIONS OF THE 22X10 AND 18X10 SUPPLY DUCTS
 THROUGH THE 1-HR FIRE-RATED PARTITION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  