Plan Review Notes
Plan Review Notes For Permit 19010326
Permit Number 19010326
Review Stop B
Sequence Number 1
Notes
Date Text
2019-02-05 07:23:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010326
 ADD: 1921 S DIXIE HWY
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 04/2019
 ACTION: DENIED
  
 1) SHEET AD1.1 SHOWS ON THE FRONT OF THE BUILDING THE
 REMOVAL OF EXISTING WINDOWS (D1) AND THE REMOVAL OF
 TERRA COTTA BLOCK BENEATH THE WINDOW FRAME (D9) FOR THE
 NEW STOREFRONT OPENING. SHEET 017_A7.0.2 SHOWS AN
 EXTERIOR STOREFRONT ELEVATION DETAIL 3/ A7.03. IN THIS
 DETAIL BELOW THE WINDOW IT SHOWS CONCRETE BLOCKWORK AND
 A NEW REINFORCED CONCRETE SILL. PLEASE SPECIFY IN THE
 DEMO SHEET IF THE TERRA COTTA BLOCK BENEATH THE OLD
 WINDOW OPENING IS TO BE REMOVED? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2A) SHEET 027_S3.1 SECTION 4 FOR A NEW WALL OPENING.
 THE PLAN SHOWS 2 NEW COLUMNS AND 2 NEW BEAMS. ABOVE THE
 UPPER BEAM THERE IS A NOTE, EXISTING TERRA COTTA IS TO
 REMAIN. SHORE EXISTING WALL AS REQUIRED FOR NEW
 OPENING. PLEASE PROVIDE ADDITIONAL INFORMATION, ARE THE
 2 COLUMNS TO BE FORMED AND POURED FIRST, THEN SHORE UP
 THE PORTION TO REMAIN AND BUILD THE BEAM UP BENEATH
 WITH REINFORCEMENT? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED FOR THE SEQUENCING
 OF WORK TO KEEP THE TERRA COTTA IN PLACE WHILE WORK IS
 BEING COMPLETED ON BOTH SIDES OF IT AND BENEATH THE
 TERRA COTTA.
  
 2B) IN THIS SAME DETAIL THERE IS A CROSS HATCHED
 SECTION OF WALL BENEATH A LOWER BEAM, DOES THIS ALSO
 REPRESENT TERRA COTTA? BENEATH THIS AREA THERE IS A
 SECTION SHOWN WITH NOTHING, NOT HATCHED, WHAT DOES THIS
 REPRESENT? 107.2.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3) SHEET S1.2 AND S3.1 BOTH SHOW BOLTED AND WELDED
 CONNECTIONS. PLEASE HAVE A 3RD PARTY ENGINEER DO A
 JOBSITE INSPECTION OF ALL BOLTED AND WELDED STEEL
 CONNECTIONS, ALL OTHER INSPECTIONS WILL BE ACCOMPLISHED
 BY CITY INSPECTORS.
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 4) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 5) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 6) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 9) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 10) SHEET 026_S2.1 COMPONENTS AND CLADDING WIND DESIGN
 PRESSURES INDICATE THE SAME PRESSURES FOR ROOF ZONES 2
 & 3. THE PARAPET IS ONLY 3 FEET TALL ON THE EAST SIDE
 OF THE BUILDING AND A PORTION OF THE SOUTH SIDE OF THE
 BUILDING, TO TAKE THE REDUCED FACTOR FOR ROOF ZONE 3
 THE PARAPET NEEDS TO BE A MINIMUM OF 3 FEET TALL AROUND
 ALL OF THE PERIMETER OF THE BUILDING. PALM BEACH COUNTY
 ARIAL MAPS SHOW THERE IS NO 3 FOOT ALL THE WAY AROUND
 THE PERIMETER OF THIS BUILDING.
  
 ASCE 7-10 FIGURE 30.4-2A. FOOTNOTE 5. IF A PARAPET IS
 EQUAL TO OR HIGHER THAN 3 FEET IS PROVIDED AROUND THE
 PERIMETER OF THE ROOF WITH 0<7 DEGREES THE NEGATIVE
 VALUE OF GCP IN ZONE 3 SHALL BE EQUAL TO THOSE IN ZONE
 2 AND THE POSITIVE VALUES OF GCP IN ZONES 2 AND 3 SHALL
 BE EQUAL TO THOSE IN WALL ZONES 4 AND 5 RESPECTIVELY,
 SEE FIGURE 30.4-1.
  
 11) THE VALUE OF THIS PERMIT IS STATED AT $738,000.00
 DOLLARS IN VALUE. PLEASE ON THE CONTRACTORS LETTER HEAD
 INDICATE WHERE 20% OF THIS VALUE ($147,600.00) IS BEING
 SPENT IN ACCESSIBILITY UPGRADES. PLEASE NOTE IN THE
 ORDER THAT THE MONIES ARE TO BE SPENT, THERE IS A NOTE
 ON THE SITE PLAN NOT IN THE SCOPE OF WORK, AND AN
 ACCESSIBLE PARKING LOT WOULD BE THE LAST ITEM WHERE
 MONIES WOULD NEED TO BE SPENT.
  
 2017 FBC-ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF
 ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE
 ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO
 THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL
 SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE
 MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE
 COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 12) NEITHER THE LIFE SAFETY PLAN NOR THE FLOOR PLAN
 A1.1.2. SHOW IF THE FRONT OR REAR EGRESS DOORS ARE AN
 ACCESSIBLE EGRESS.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 13) SHEET 010_A1.1.2. IN THE TENANT SPACE 117 IN THE
 CORRIDOR 118 WHERE THE ACCESSIBLE DRINKING FOUNTAINS
 ARE LOCATED PLEASE PROVIDE COMPLIANCE WITH THE:
  
 2017 FBC-ACCESSIBILITY CODE SECTION 305.7MANEUVERING
 CLEARANCE. WHERE A CLEAR FLOOR OR GROUND SPACE IS
 LOCATED IN AN ALCOVE OR OTHERWISE CONFINED ON ALL OR
 PART OF THREE SIDES, ADDITIONAL MANEUVERING CLEARANCE
 SHALL BE PROVIDED IN ACCORDANCE WITH 305.7.1 AND
 305.7.2.
 304.3 SIZE. TURNING SPACE SHALL COMPLY WITH 304.3.1 OR
 304.3.2.
  
 14) SHEET 022_A10.1.1. DETAIL # 5, UNDER COUNTER SINK,
 PLEASE SHOW COMPLIANCE WITH THE:
  
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO