2019-01-24 12:40:56 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| GAS COMMENTS: |
| |
| 1. IT IS UNCLEAR ON THE PLAN IF THE GAS APPLIANCES ARE |
| NEW OR EXITING TO REMAIN PLEASE CLARIFY. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 2. IF THE THE GAS APPLIANCES ARE GOING TO BE NEW IN THE |
| SAME LOCATION THE SIZING OF THE EXISTING SYSTEM SHALL |
| BE VERIFIED TO MEET SIZING REQUIREMENTS AND IN GOOD |
| WORKING ORDER. PLEASE PROVIDE THE FOLLOWING |
| INFORMATION. |
| A) A GAS RISER SHOWING, TYPE OF PIPE, SIZE OF PIPE, |
| SYSTEM PRESSURE, BTU LOAD OF EACH APPLIANCE AND |
| DISTANCE FROM THE METER TO FURTHEST APPLIANCE. PER FBC |
| RES G2413.4 |
| B)SIZING TABLE USED TO SIZE SYSTEM. PER FBC RES G2413.4 |
| C)COMBUSTION AIR CALCULATIONS.PER FBC RES G2407.1 |
| D) THE SIZE, TYPE, LENGTH, LOCATION OR A DETAIL SHOWING |
| PIPING AND MANUFACTURE SPECIFICATION FOR THE WATER |
| HEATER VENTING. PER FBC RES G2427.1 |
| E) MANUFACTURE SPECIFICATIONS FOR ALL NEW GAS |
| APPLIANCES. PER WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.PER WPB AMEND TO FBC |
| 107.2.1 AND FBC RES G2401.1 |
| |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |