2019-01-23 07:48:55 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 |
| 2. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR |
| THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC |
| 107.1, 107.2.1, 107.3.5.1.2 |
| 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; WPB FBC 107.2.1 |
| 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| 6. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| 7. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN |
| KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. |
| NEC 210.8; FBC RE E3902.6 |
| 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC |
| 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |