2019-02-07 15:53:50 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ONE PERSON SHOULD TAKE RESPONSIBILITY FOR ELECTRICAL |
| PLAN. THERE ARE 2 IDENTICAL SHEETS, ONE SIGNED/SEALED |
| BY THE AOR, AND ONE SIGNED BY THE ELECTRICAL |
| CONTRACTOR. DECIDE WHICH PLAN WILL BE SUBMITTED FOR |
| REVIEW AND REMOVE OTHER SHEET. WPB FBC 107.1 |
| 2. PLANS SHOW ITEMS ON DEMOLITION PLAN AS BEING |
| REMOVED, AND THEN SHOW THE SAME ITEMS ON FLOOR PLAN AS |
| EXISTING. ARE THESE ITEMS BEING DEMOLISHED OR NOT? PLAN |
| NEEDS TO REFLECT THE WORK PROPOSED. PROVIDE SCOPE OF |
| WORK DESCRIPTION AND PLAN TO MATCH. WPB FBC 107.2.1 |
| 3. PROVIDE A MORE CLEAR REPRESENTATION OF THE LOCATION |
| OF ELECTRICAL PANELS. OVERCURRENT PROTECTIVE DEVI ES |
| ARE NOT PERMIITED IN CLOTHES CLOSETS AND IT IS NOT |
| POSSIBLE TO DETERMINE THE LOCATION OF THE PANELS FROM |
| THIS DRAWING. WPB FBC 107.2.1; NEC 240.24(D) |
| 4. THERE ARE KEYNOTES LISTED THAT DO NOT APPEAR ON |
| PLAN, SUCH AS KEYNOTE 7. THERE ARE KEYNOTES LISTED THAT |
| DO NOT PERTAIN TO ELECTRICAL ITEMS AND SHOULD BE |
| REMOVED FROM ELECTRICAL PLAN, SUCH AS KEYNOTE 9. |
| PROVIDE CLARIFICATIONS AND/OR CORRECTIONS. WPB FBC |
| 107.2.1 |
| 5. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC EX 607.1.1 |
| OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12 |
| 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS |
| FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS |
| SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A |
| RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES |
| NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION. |
| NEC 210.52(C)(1) |
| 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |