2019-02-07 15:53:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONE PERSON SHOULD TAKE RESPONSIBILITY FOR ELECTRICAL
 PLAN. THERE ARE 2 IDENTICAL SHEETS, ONE SIGNED/SEALED
 BY THE AOR, AND ONE SIGNED BY THE ELECTRICAL
 CONTRACTOR. DECIDE WHICH PLAN WILL BE SUBMITTED FOR
 REVIEW AND REMOVE OTHER SHEET. WPB FBC 107.1
 2. PLANS SHOW ITEMS ON DEMOLITION PLAN AS BEING
 REMOVED, AND THEN SHOW THE SAME ITEMS ON FLOOR PLAN AS
 EXISTING. ARE THESE ITEMS BEING DEMOLISHED OR NOT? PLAN
 NEEDS TO REFLECT THE WORK PROPOSED. PROVIDE SCOPE OF
 WORK DESCRIPTION AND PLAN TO MATCH. WPB FBC 107.2.1
 3. PROVIDE A MORE CLEAR REPRESENTATION OF THE LOCATION
 OF ELECTRICAL PANELS. OVERCURRENT PROTECTIVE DEVI ES
 ARE NOT PERMIITED IN CLOTHES CLOSETS AND IT IS NOT
 POSSIBLE TO DETERMINE THE LOCATION OF THE PANELS FROM
 THIS DRAWING. WPB FBC 107.2.1; NEC 240.24(D)
 4. THERE ARE KEYNOTES LISTED THAT DO NOT APPEAR ON
 PLAN, SUCH AS KEYNOTE 7. THERE ARE KEYNOTES LISTED THAT
 DO NOT PERTAIN TO ELECTRICAL ITEMS AND SHOULD BE
 REMOVED FROM ELECTRICAL PLAN, SUCH AS KEYNOTE 9.
 PROVIDE CLARIFICATIONS AND/OR CORRECTIONS. WPB FBC
 107.2.1
 5. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC EX 607.1.1
 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1)
 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  