Plan Review Notes For Permit 18120923 |
Permit Number |
18120923 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-01-08 06:50:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN SIGNED BY PERSON RESPONSIBLE | | FOR THE DESIGN FOR REVIEW SHOWING LOCATION AND SIZE OF | | NEW PANEL AND LOCATION OF NEW RECEPTACLES IN KITCHEN | | PLUS ANY ADDITIONAL ELECTRICAL WORK. NOTE ON PLAN | | STATING "INSTALL RECEPTACLES TO CODE" IS NOT | | SUFFICIENT.FS 481.229; WPB FBC 107.2.1, 107.3.5.1.2 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | | | |
|