2019-01-24 09:45:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 GAS COMMENTS: DENIED
 1. UPON REVIEW OF HISTORY IN PERMIT RECORDS SEARCH THE
 FOLLOWING IS DETERMINED.
 A. THERE IS AN EXISTING GAS RANGE (50.2 MBTU) IN THE
 EXISTING KITCHEN WITH 52' 3/4" CSST DEVELOPED LENGTH
 FROM EXISTING METER (PER PERMIT #16020172 PLANS DATED
 1/13/2016. THIS SHALL BE INCORPORATED INTO DRAWINGS AND
 CALCULATIONS, REVISING LENGTH AS NECESSARY IN REGARD TO
 RELOCATION OF EXISTING METER PER WPB FBC 107.2.1 AND
 SHALL BE RESUBMITTED IN ACCORDANCE WITH THE
 REQUIREMENTS OF WPB FPC SECTION 105.
 B. PER PERMIT #06100851 PLAN APPROVED 10/31/06, THE
 EXISTING LP TANK IS NOTED AS APPROXIMATELY 10' FROM THE
 EXISTING METER. PER WPB FBC 107.2.1 SHOW LOCATION OF
 EXISTING TANK IN RELATIONSHIP TO THE NEW CONSTRUCTION
 SHOWING COMPLIANCE WITH THE PROVISIONS OF NFPA 58
 SECTION 6.4.2.
  
 2. PROVIDE MANUFACTURER'S SPEC FOR NAVEN #NPE-240A-OD
 TANKLESS WATER HEATER PER WPB FBC 107.2.1 AND RES FBC
 G2404.3.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
2019-01-22 16:10:30JESMITH PUT PLANS BACK IN BIN R27 1/22/19