Date |
Text |
2019-01-24 09:45:34 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| GAS COMMENTS: DENIED |
| 1. UPON REVIEW OF HISTORY IN PERMIT RECORDS SEARCH THE |
| FOLLOWING IS DETERMINED. |
| A. THERE IS AN EXISTING GAS RANGE (50.2 MBTU) IN THE |
| EXISTING KITCHEN WITH 52' 3/4" CSST DEVELOPED LENGTH |
| FROM EXISTING METER (PER PERMIT #16020172 PLANS DATED |
| 1/13/2016. THIS SHALL BE INCORPORATED INTO DRAWINGS AND |
| CALCULATIONS, REVISING LENGTH AS NECESSARY IN REGARD TO |
| RELOCATION OF EXISTING METER PER WPB FBC 107.2.1 AND |
| SHALL BE RESUBMITTED IN ACCORDANCE WITH THE |
| REQUIREMENTS OF WPB FPC SECTION 105. |
| B. PER PERMIT #06100851 PLAN APPROVED 10/31/06, THE |
| EXISTING LP TANK IS NOTED AS APPROXIMATELY 10' FROM THE |
| EXISTING METER. PER WPB FBC 107.2.1 SHOW LOCATION OF |
| EXISTING TANK IN RELATIONSHIP TO THE NEW CONSTRUCTION |
| SHOWING COMPLIANCE WITH THE PROVISIONS OF NFPA 58 |
| SECTION 6.4.2. |
| |
| 2. PROVIDE MANUFACTURER'S SPEC FOR NAVEN #NPE-240A-OD |
| TANKLESS WATER HEATER PER WPB FBC 107.2.1 AND RES FBC |
| G2404.3. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| |
2019-01-22 16:10:30 | JESMITH PUT PLANS BACK IN BIN R27 1/22/19 |