Plan Review Notes
Plan Review Notes For Permit 18120896
Permit Number 18120896
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-31 18:29:00RESIDENTIAL (R3)ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 2- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET
 A-7 DON'T MATCH DESIGN PRESSURES SHOWN ON SHEET S-5.
 REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: PRODUCT APPROVALS WILL BE REVIEWED WHEN DESIGN
 PRESSURES ARE CLARIFIED.
  
 3- REVISE/CLARIFY ALL ROOF LOADS. INFORMATION SHOWN ON
 SHEET S-2 AND SHEET S-4 DOESN'T MATCH. REVISE AS
 REQUIRED AND CLEARLY SPECIFY ROOF TOP CHORD AND BOTTOM
 CHORD DEAD AND LIVE LOADS. NOTE: SEE NOTES "B" AND "G"
 OF TABLE R301.5 FBC-RESIDENTIAL FOR MINIMUM LIVE LOAD
 REQUIRED IN ATTICS.
  
 4- ROOF SHEATHING:
 A)CLARIFY/REVISE ROOF SHEATHING NAILING SPECIFICATIONS.
 INFORMATION SHOWN ON SHEET S-2, S-3 AND S-4 DOESN'T
 MATCH. REVISE AS REQUIRED TO MATCH. NOTE: SEC.
 R803.2.3.1 FBC-RESIDENTIAL REQUIRES 8D COMMON RING
 SHANK NAILS MIN.
  
 B) REVISE GABLE END DIAGRAM SHOWN ON SHEET S-3 UNDER
 THE PLYWOOD ROOF SHEET DIAPHRAGM SCHEDULE. ACCORDING TO
 FIGURE R803.2.3.1 WHOLE GABLE END IS CONSIDERED AS ROOF
 ZONE #3. REVISE AS REQUIRED.
  
 C) INFORMATION ON TYPICAL ROOF SHEATHING DETAIL ON
 SHEET S-3 IS NOT LEGIBLE. THERE IS INFORMATION THAT IS
 OVERLAPPED. REVISE AS REQUIRED. SEC.107.2.1 CITY
 AMENDMENTS. ALSO, THEE ARE MANY AREAS IN THIS SHEET
 REFERENCING THE 2010 FBC. CURRENT CODE IS THE 2017 FBC.
 UPDATE AS REQUIRED. CHAPTER 553 F.S.
  
 5-THE SOIL BEARING CAPACITY (2500 PSF)SPECIFIED BY THE
 ENGINEER OF RECORD AND SOIL BEARING CAPACITY SHOWN ON
 THE SOIL TEST REPORT (2000 PSF) DOESN'T MATCH.
 COORDINATE AND REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL.
  
 6- SOIL TEST REPORT TO MATCH THE ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 7- SPECIFY CARBON MONOXIDE ALARMS FOR ALL EXISTING
 BEDROOMS ALSO AS REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL.
  
 8- ARCHITECTURAL PLANS SHOW CBS WALLS THAT DON'T MATCH
 SURVEY. CLARIFY/REVISE AS REQUIRED. ARE THESE PROPOSED
 WALLS?. IF SO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS UNDER A SEPARATE FENCE PERMIT.
 COORDINATE WITH ZONING. SEC. 105.1 CITY AMENDMENTS.
  
 9- FLOOR PLANS TO SPECIFY RVALUE INSULATION AT ADJACENT
 WALL BETWEEN GARAGE AND A/C AREAS AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION. NOTE: THERE IS A
 CONCRETE BLOCK WALL AND METAL FRAMED WALL. SEE FLOOR
 PLAN.
  
 10- ENERGY CALCULATIONS:
 A)THE BUILDING?S OWNER, THE OWNER?S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE,
 ETC. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) EXTERIOR WALL INSULATION SPECIFIED ON ITEM #9
 DOESN'T MATCH PLANS AND NEED TO COORDINATE INSULATION
 R-VALUE FOR ADJACENT WALL BETWEEN GARAGE AND MAIN
 HOUSE. NOTE: CONCRETE BLOCK WALL AND METAL FRAMED WALL.
 SEE PLANS.
  
 D)CEILING R-VALUE INSULATION SPECIFIED ON ITEM #10
 DOESN'T MATCH ARCHITECTURAL PLANS.
  
 11- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT
 IS SPECIFYING R-19 ICYNENE SPRAY INSULATION. PROVIDE
 ICC EVALUATION REPORT (2 COPIES) FOR THE ICYNENE
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 12-PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]