Plan Review Notes
Plan Review Notes For Permit 18120893
Permit Number 18120893
Review Stop E
Sequence Number 1
Notes
Date Text
2019-01-10 11:06:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A DISCONNECT NEXT TO METER, A
 MAIN PANEL, AND A SUB-PANEL. ON THE FLOOR PLAN, THERE
 IS ONLY A METER CAN AND SUB-PANEL SHOWN. WHERE IS THE
 MAIN PANEL LOCATED? PANEL SCHEDULE FOR MAIN PANEL SAYS
 THAT IT IS 200 AMP, BUT RISER DIAGRAM SHOWS IT AS 150
 AMP. PROVIDE CLARIFICATION AND/OR CORRECTIONS TO
 CLEARLY SHOW LOCATIONS OF ALL PANELS AND A CORRECT
 RISER DIAGRAM. NEC 215.5, 230, 250.50, 250.94, 408.30;
 FBC RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 2. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3
 4. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 5. AT LEAST ONE RECEPTACLE OUTLET MUST BE INSTALLED IN
 GARAGE FOR EACH MOTOR VEHICLE SPACE. PROVIDE
 CORRECTION. FBC RE E3901.9
 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 7. SMOKE ALARM REQUIRED IN LIVING ROOM AS IT IS A ROOM
 THAT CAN BE USED FOR SLEEPING PURPOSES. PROVIDE
 CORRECTION. FBC RE R314.3
 8. FOR DOWNSTAIRS BATH, A GFCI PROTECTED RECEPTACLE
 OUTLET ON A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF
 BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D);
 FBC RE E3703.4, E3901.6
 9. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 10. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION FOR GYM DOOR. NEC
 210.70(A)(2)(B), FBC RE E3903.3
 11. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE
 OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING
 UNIT. NEC 210.52(E)(3); FBC RE E3901.7
 12. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER