Text |
2019-01-10 11:06:43 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER DIAGRAM SHOWS A DISCONNECT NEXT TO METER, A |
| MAIN PANEL, AND A SUB-PANEL. ON THE FLOOR PLAN, THERE |
| IS ONLY A METER CAN AND SUB-PANEL SHOWN. WHERE IS THE |
| MAIN PANEL LOCATED? PANEL SCHEDULE FOR MAIN PANEL SAYS |
| THAT IT IS 200 AMP, BUT RISER DIAGRAM SHOWS IT AS 150 |
| AMP. PROVIDE CLARIFICATION AND/OR CORRECTIONS TO |
| CLEARLY SHOW LOCATIONS OF ALL PANELS AND A CORRECT |
| RISER DIAGRAM. NEC 215.5, 230, 250.50, 250.94, 408.30; |
| FBC RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1 |
| 2. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| 801.2, OR 901.2 AS APPLICABLE. |
| 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE PANEL INCLUDING INFORMATION FROM THE POWER |
| COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC |
| RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS |
| IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 |
| 4. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| OUTLETS IN GARAGE INCLUDING THE GARAGE DOOR OPENER. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| 5. AT LEAST ONE RECEPTACLE OUTLET MUST BE INSTALLED IN |
| GARAGE FOR EACH MOTOR VEHICLE SPACE. PROVIDE |
| CORRECTION. FBC RE E3901.9 |
| 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1 |
| 7. SMOKE ALARM REQUIRED IN LIVING ROOM AS IT IS A ROOM |
| THAT CAN BE USED FOR SLEEPING PURPOSES. PROVIDE |
| CORRECTION. FBC RE R314.3 |
| 8. FOR DOWNSTAIRS BATH, A GFCI PROTECTED RECEPTACLE |
| OUTLET ON A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF |
| BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); |
| FBC RE E3703.4, E3901.6 |
| 9. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| 10. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| LEVEL ACCESS. PROVIDE CORRECTION FOR GYM DOOR. NEC |
| 210.70(A)(2)(B), FBC RE E3903.3 |
| 11. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE |
| OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING |
| UNIT. NEC 210.52(E)(3); FBC RE E3901.7 |
| 12. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| FBC EC C405.1, R404.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |