2019-01-28 15:24:10 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| JOSEAN A. DUPREY |
| BUILDING PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6716 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. THE DRAWING SHEET "SITE" NOTE #4 INDICATES THE |
| CONSTRUCTION DOCUMENTS HAVE BEEN PREPARED IN ACCORDANDE |
| WITH FBC 2014. THE CURRENT CODE IS THE FBC 2017. PLEASE |
| REVISED THE DOCUMENTS PREPARED UNDER FBC 2014 MEET THE |
| FBC 2017 REQUIREMENTS. |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| EDITION |
| FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| 2. DOORS & WINDOWS: |
| 2A. FOR THE EAST ELEVATION AND NORTH ELEVATION DOORS IS |
| NOT CLEAR WICH PRODUCT IS GOING TO BE USED. PLEASE |
| INDICATE OR PROVIDE THE PRODUCT APPROVAL FOR THIS DOOR. |
| FBC 107 |
| 2B. PLEASE PROVIDE THE FOLLOWING INFORMATION: |
| |
| WINDOWS WITH DIMENSIONS OF ROUGH OPENINGS. IF NO |
| CHANGES ARE TO BE MADE TO THE ROUGH OPENINGS, PROVIDE |
| STATEMENT THAT WINDOWS WILL BE LIKE FOR LIKE. IF |
| OPENINGS ARE ALTERED, PROVIDE FRAMING PLAN PER FBCR |
| CHAPTER 6. |
| |
| IDENTIFY THE EGRESS WINDOW AND PROVIDE DIMENSION FROM |
| THE FINISH FLOOR TO THE WINDOWS SILL. FBC 107; FBC 1030 |
| |
| 3. THE FOUNDATION PLAN INDICATES NEW FOOTINGS WITH |
| AUGER CAST PILES DESIGN THAT WILL BE PART OF THE NEW |
| STRUCTURAL SYSTEM. PLEASE PROVIDE THE CALCULATIONS, |
| GEOTECHNICAL REPORT RECOMENDATION FOR THE FOUNDATIONS |
| AND/OR MORE SPECIFIC DETAILS IN REGARDS THE AUGER CAST |
| PILE FOUNDATIONS OF THIS NEW STRUCTURAL SYSTEM. WILL BE |
| HELPFUL IF AN EXISTING FOUNDATION PLAN CAN BE PROVIDED. |
| FBC 107 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |