2019-04-15 17:17:14 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18120892 |
| 4/15/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS A2.0 & M1.1: MISSING FIRE DAMPERS FOR THE 8/8 |
| TRANSFER DUCT AND THE 22/14 O/A DUCT PENETRATING THE |
| FIRE-RATED CHEM STORAGE ROOM WALLS- SECTION 607.5.2 FBC |
| M. |
| |
| 2) A2.0 & M1.1: THE 6/6 EXHAUST DUCT FROM THE CHEM |
| STORAGE ROOM MUST BE ENCLOSED IN FIRE-RESISTANT |
| CONSTRUCTION FROM THE POINT OF THE FIRE-RATED WALL |
| PENETRATION TO THE OUTLET TERMINAL- SECTION 510.7.3 FBC |
| M. |
| |
| 3) A100, A603, & M1.1: AS PREVIOUSLY NOTED, IT APPEARS |
| THAT AIR IS BEING RECIRCULATED VIA TRANSFER GRILLS FROM |
| THE SOLID ROOM INTO THE HALLWAY WHICH IS PROHIBITED- |
| SEE TABLE 403.3.1.1 FOOTNOTE G- RECIRCULATION OF AIR |
| FROM THE LAB ROOMS IS PROHIBITED WITH THE EXCEPTION OF |
| 10% OF THE AIRSTREAM FROM THE SPACES IS PERMITTED TO BE |
| RECIRCULATED. THE ROOM IS NOT LABELED "LAB" HOWEVER |
| THERE IS A FUME HOOD IN THE ROOM AND OTHER PROCESSING |
| EQUIPMENT AND OVENS. |
| |
| 4) A100, A603, & M1.1: SHOW THE EXHAUST DUCT RUN AND |
| TERMINATION LOCATION FOR THE EXHAUST HOOD IN THE |
| MICROBIOLOGY ROOM- SECTION 510.6.7 FBC M. |
| |
| 5) A100, A603, & M1.1: PLEASE PROVIDE A NARRATIVE THAT |
| DESCRIBES THE PROCESSES THAT OCCUR UNDER THE HOODS IN |
| THE LAB, SOLIDS, AND MICROBIOLOGY ROOMS. A) PROVIDE A |
| SEQUENCE OF OPERATION THAT INCLUDES HOW MAKE UP AIR |
| WILL BE AUTOMATICALLY PROVIDED- SECTION 510.6.5 FBC M |
| B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE HOODS, FANS, AND |
| EXHAUST DUCTWORK- SECTIONS 304.1 & 510.6.3 FBC M. |
| |
| 6) M1.100: VERIFY ALL EXHAUST OUTLET CLEARANCES ARE IN |
| COMPLIANCE WITH SECTION 501.3.1 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |