2019-04-19 15:01:50 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18120892 |
| ADD: 4375 EASLEY DR. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-835-7406 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JAN. 28/2019 |
| ACTION: DENIED |
| |
| 1) OK. |
| |
| 2) OK. |
| |
| ORIGINAL COMMENT: |
| 3) THE SHEET 023-S-2 UNDER THE HEADING OF FOUNDATIONS |
| NOTE # 1 INDICATES THERE IS A SOILS REPORT PREPARED BY |
| FEDERAL ENGINEERING AND TESTING, DATED AUGUST 24, 2018. |
| PLEASE SUBMIT A PAPER ORIGINAL SIGNATURE AND SEALED OR |
| SUBMIT ELECTRONICALLY WITH AN ELECTRONIC SIGNATURE. |
| |
| RESPONSE: |
| SOIL TEST REPORT SUBMITTED DOESN'T HAVE A DIGITAL |
| SIGNATURE. UPLOAD REPORT WITH ENGINEER'S DIGITAL |
| SIGNATURE OR SUBMIT HARD COPIES WITH ORIGINAL SEAL AND |
| SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING |
| DOCUMENTS FOR PUBLIC RECORDS. |
| |
| 4A) OK. |
| |
| 4B) OK. |
| |
| 5) PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. CONTRACTOR TO ADVICE IF SUBMITTING PRODUCT |
| APPROVALS AS DEFERRED SUBMITTAL. PROVIDE COMPLETE |
| INFORMATION PRIOR TO INSTALLATION TO AVOID |
| CONFLICTS/DELAYS. ALL PRODUCT APPROVALS NEED TO BE |
| APPROVED IN WRITING BY DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL) |
| |
| (A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE AND OR INSULATION, |
| |
| 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| THE SPECIFIC SITE. |
| |
| 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 9) OK. NOTED ON DRAWINGS. |
| THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE THE |
| ADDITION IS TO HAVE A BAR JOIST AND METAL DECK ROOF |
| SYSTEM. PLEASE HAVE A 3RD PARTY ENGINEER REVIEW ALL |
| WELDED JOINTS AND BOLTED JOINTS AND SUPPLY A SIGNED AND |
| SEALED LETTER OF THE INSPECTIONS AT THE TIME OF THE |
| WINDOW BUCK INSPECTION AND BEFORE THE INTERIOR FRAMING |
| INSPECTION. IF THERE IS ANY QUESTIONS IN REGARDS TO |
| BUILDING INSPECTIONS PLEASE CONTACT THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD AT 561-805-6666. |
| WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| 2017 FBC-B 2204.2 BOLTING. |
| |
| 10) NEW COMMENTS ON ENERGY CALCULATIONS: |
| A) NEED ARCHITECT'S NAME AND LICENSE NUMBER ON THE |
| ENERGY CALCULATIONS. SEE FOOTNOTE ON CERTIFICATIONS |
| PAGE. ALSO. SEE SEC. C103.1.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| B) NEED THE OWNER'S OR OWNER'S AUTHORIZED AGENT TO |
| CERTIFY THE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| C103.1.1.2 FBC-ENERGY CONSERVATION |
| |
| |
| 11) OK. |
| |
| |
| 12) OK. |
| |
| 13) OK. |
| |
| 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |