Plan Review Notes
Plan Review Notes For Permit 18120892
Permit Number 18120892
Review Stop P
Sequence Number 1
Notes
Date Text
2019-01-28 12:21:401ST REVIEW: 18120892
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2 THE WATER
 CLOSET SHALL BE POSITIONED WITH A WALL OR PARTITION TO
 THE REAR AND TO ONE SIDE. THE CENTERLINE OF THE WATER
 CLOSET SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM
 FROM THE SIDE WALL OR PARTITION.
  
 3. A OVERFLOW ROOF DRAIN OR SCUPPER IS REQUIRED. PER
 FBC PL 1108.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  