Plan Review Notes
Plan Review Notes For Permit 18120892
Permit Number 18120892
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-28 10:06:342017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120892
 ADD: 4375 EASLEY DR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-835-7406
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 28/2019
 ACTION: DENIED
  
 1) IN REVIEWING THE COVERSHEET THE LIFE SAFETY SHEET
 005-A-020 THE PLANS INDICATE THE BUILDING AND ADDITION
 IS TO BE FIRE SPRINKLERED. PLEASE SUBMIT FIRE SPRINKLER
 PLANS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING.
 107.3.51.1. (5.) FIRE SUPPRESSION SYSTEMS SHALL
 INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS CAN BE SHOP DRAWINGS UNDER A
 SEPARATE PERMIT.
  
 FIRE SPRINKLERS 61G15-32.004 DESIGN OF WATER BASED FIRE
 PROTECTION SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE: (A-M).
  
 2) THE COVERSHEET LIST THE TOTAL UNDER ROOF SQUARE FEET
 OF THE BUILDING AS 7,675 SQ. FT. THE NEW LAB IN ITSELF
 IS OVER THE 10% OF THE BUILDING. THE EXISTING LAB WOULD
 APPEAR TO BE AROUND 600 SQ. FT. OR A TOTAL AREA OF
 1,949 SQ. FT. WHICH HAS OR COULD HAVE HAZARDOUS
 CHEMICALS. PLEASE PROVIDE THE CHEMICALS TO BE USED IN
 THE LAB AND MSDS SHEETS, AMOUNT OF CHEMICALS THAT ARE
 TO BE USED IN EACH OF THE LAB AREAS, IF THE CHEMICALS
 ARE TO BE STORED IN 1 HOUR RATED FIRE CABINETS. THE
 PLANS FAIL TO SHOW A FIRE SEPARATION (FIRE BARRIERS)
 FOR CONTROL AREAS FROM THE REMAINDER OF THE BUILDING.
  
 2017 FBC-B 307.1 HIGH-HAZARD GROUP H OCCUPANCY
 INCLUDES, AMONG OTHERS, THE USE OF A BUILDING OR
 STRUCTURE, OR A PORTION THEREOF, THAT A PHYSICAL OR
 HEALTH HAZARD IN QUANTITIES IN EXCESS OF THOSE ALLOWED
 IN CONTROL AREAS COMPLYING WITH SECTION 414, BASED ON
 THE MAXIMUM ALLOWABLE QUANTITY LIMITS FOR CONTROL AREAS
 SET FORTH IN TABLES 307.1(1) AND 307.1(2).
 PLEASE SEE SECTION 414.2 OF THE 2017 FBC-B FOR CONTROL
 AREAS.
  
 3) THE SHEET 023-S-2 UNDER THE HEADING OF FOUNDATIONS
 NOTE # 1 INDICATES THERE IS A SOILS REPORT PREPARED BY
 FEDERAL ENGINEERING AND TESTING, DATED AUGUST 24, 2018.
 PLEASE SUBMIT A PAPER ORIGINAL SIGNATURE AND SEALED OR
 SUBMIT ELECTRONICALLY WITH AN ELECTRONIC SIGNATURE.
  
 4A) PLEASE REVIEW SHEET 023-S-2 THE NEGATIVE VALUES
 (PRESSURES) FOR VULT AND VASD ARE THE SAME THE VASD
 VALUES SHOULD BE MULTIPLIED BY THE 0.6 TO BECOME VASD.
 2017 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 THE WALL NEGATIVE PRESSURES ALSO APPEAR FOR THE WALL
 ALSO APPEAR 3.5 LBS. LOW PRESSURES ARE TAKEN AT 15 FEET
 ABOVE GRADE, THAT IS THE LAST PRESSURE GIVEN IN THE
 TABLES IN 1609 AND IN ASCE 7-10.
  
 4B) PRESSURES (NEGATIVE) GIVEN ON SHEET 012-A-200 FOR
 THE WALL ALSO APPEAR 3.5 LBS. LOW PRESSURES ARE TAKEN
 AT 15 FEET ABOVE GRADE THAT IS THE LAST PRESSURE GIVEN
 IN THE TABLES IN 1609 AND IN ASCE 7-10.
  
 5) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE AND OR INSULATION,
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE THE
 ADDITION IS TO HAVE A BAR JOIST AND METAL DECK ROOF
 SYSTEM. PLEASE HAVE A 3RD PARTY ENGINEER REVIEW ALL
 WELDED JOINTS AND BOLTED JOINTS AND SUPPLY A SIGNED AND
 SEALED LETTER OF THE INSPECTIONS AT THE TIME OF THE
 WINDOW BUCK INSPECTION AND BEFORE THE INTERIOR FRAMING
 INSPECTION. IF THERE IS ANY QUESTIONS IN REGARDS TO
 BUILDING INSPECTIONS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666.
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 10) ENERGY CODE. THE APPLICANT HAS SUBMITTED THE ENERGY
 GAUGE SUMMIT ASHRAE 90.1 ENERGY COST BUDGET OPTION OF
 CODE COMPLIANCE FOR ENERGY. THE QUESTION THAT I HAVE IS
 ON THE INPUT DATA REPORT PAGE 2 FOR THE EXTERIOR WALLS
 THE REPORT SHOWS WIDTH AND HEIGHT (EFFECTIVE) OF THE
 WALLS. THE QUESTION IS THE HEIGHT OF THE WALL IS GIVEN
 AT 9 FEET AND ON SHEET A-220 ALL OF THE DETAILS SHOW
 THE EXTERIOR WALL INSULATION GOING UP TO 9 FEET THE
 HEIGHT OF THE DROPPED CEILING, WHEREAS THE ROOF TOP
 INSULATION IS GIVEN AT A HEIGHT OF 12 FOOT 3 INCHES.
 PLEASE PROVIDE WHY THE EXTERIOR WALL INSULATION OR THE
 EXTERIOR SOFFIT AND FACIA WOULD NEED TO COMPLETE THE
 INSULATION TO THE ROOF LINE, TO MAKE A COMPLETE
 ENVELOPE?
  
 2017 FBC-ENERGY CODE C304.3.2.2 APPLICANT-DETERMINED
 ASSEMBLY U-FACTORS, C-FACTORS, F-FACTORS OR HEAT
 CAPACITIES. IF THE BUILDING OFFICIAL DETERMINES THAT
 THE PROPOSED CONSTRUCTION ASSEMBLY IS NOT ADEQUATELY
 REPRESENTED IN THE APPROPRIATE TABLE OF ASHRAE 90.1
 NORMATIVE APPENDIX A, THE APPLICANT SHALL DETERMINE
 APPROPRIATE VALUES FOR THE ASSEMBLY USING THE
 ASSUMPTIONS IN ASHRAE 90.1 NORMATIVE APPENDIX A.
  
 11A) THE ROOF PLAN, SHEETS 011-A-110, 039-P1.2 AND
 013-A-220 ALL REPRESENT THE ROOF PLAN. THE SHEET P1.2
 DOES GIVE THE ROOF AREA AND PARAPET TO BE DRAINED AND
 THE SIZE OF THE VERTICAL LEADERS. WHAT IS MISSING IS
 THE ANNUAL RAIN FALL. SEE 1503.4 ROOF DRAINAGE OF THE
 2017 FBC-B. UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF
 EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS
 SHALL COMPLY WITH SECTION 1503 AND THE FLORIDA BUILDING
 CODE, PLUMBING, CHAPTER 11.
  
 11B) PLEASE REVIEW SHEET 011-A-110 THE ROOF PLAN.
 DETAIL 3 INDICATES THE NEW ROOF LINE IS IN AT A HIGHER
 ELEVATION THAN THE OLD ROOF. WHEN VIEWING THE EXISTING
 ROOF LINE IN DETAIL 1 IN THE END VIEW OF THE ROOF IT
 APPEARS THAT THERE IS 2 EMERGENCY OVERFLOW SCUPPERS
 THAT WILL BE NO LONGER EFFECTIVE SINCE THE NEW ROOF
 LINE IS HIGHER? HOW OR WHERE WILL THE EMERGENCY
 OVERFLOWS BE LOCATED IN THE EXISTING ROOF?
  
 2017 FBC-B 1503.4.1 SECONDARY (EMERGENCY OVERFLOW)
 DRAINS OR SCUPPERS. WHERE ROOF DRAINS ARE REQUIRED,
 SECONDARY (EMERGENCY OVERFLOW) ROOF DRAINS OR SCUPPERS
 SHALL BE PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION
 EXTENDS ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL
 BE ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR
 ANY REASON. THE INSTALLATION AND SIZING OF SECONDARY
 EMERGENCY OVERFLOW DRAINS, LEADERS AND CONDUCTORS SHALL
 COMPLY WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF
 THE FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11.
  
 12) SHEET 015-A-401 DETAILS 3 AND 6 .
 12A) DETAIL 3 SHOWS EITHER POWER DRIVEN FASTENER OR
 EXPANSION ANCHOR BEING INSTALLED INTO THE BOTTOM OF AN
 EXISTING PRE-CAST ROOF JOIST. PLEASE GET THE STRUCTURAL
 ENGINEER TO SIGN OFF ON THIS APPLICATION SINCE THE
 BOTTOM REINFORCING MAYBE ENDANGERED OR CONCRETE MAYBE
 CHIPPED OR CRACKED EXPOSING THE BOTTOM CHORD OF
 INFORCEMENT. 107.2.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, STRESS
 DIAGRAMS, AND OTHER DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE BASIS OF
 CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO
 BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE
 AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS
 STATE LAW REQUIRES.
  
 12B) PLEASE REVIEW DETAIL 6 OF THE SAME SHEET. HIGH HAT
 IS TO BE APPLIED TO THE CORNER OF AN EXISTING BEAM, THE
 PLANS SHOW ONE PIECE OF HIGH-HAT FLANGE AT THE CORNER
 OF THE BEAM THERE IS NO MENTION OF HOW TO ANCHOR THE
 HIGH HAT AND WHAT DISTANCE TO STAY AWAY FROM THE CORNER
 TO KEEP FROM THE CONCRETE FROM SPAWLING. . 107.2.1.2
 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE
 DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION
 AND THE BASIS OF CALCULATIONS. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE
 BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR
 ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE AS STATE LAW REQUIRES.
  
 13) THE VALUE OF THE PROJECT WAS REDUCED FROM
 $1,686,678.00 TO $300,000.00 IN VALUE. PLEASE PROVIDE
 AN ITEMIZED LIST TO SEE WHAT WAS REMOVED FROM THE
 PROJECT VALUE, INCLUDE THE LINE ITEM VALUE FOR EACH
 ITEM REMOVED.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  