2019-01-28 10:06:34 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18120892 |
| ADD: 4375 EASLEY DR. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-835-7406 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JAN. 28/2019 |
| ACTION: DENIED |
| |
| 1) IN REVIEWING THE COVERSHEET THE LIFE SAFETY SHEET |
| 005-A-020 THE PLANS INDICATE THE BUILDING AND ADDITION |
| IS TO BE FIRE SPRINKLERED. PLEASE SUBMIT FIRE SPRINKLER |
| PLANS. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING. |
| 107.3.51.1. (5.) FIRE SUPPRESSION SYSTEMS SHALL |
| INCLUDE: |
| SCHEMATIC FIRE SPRINKLERS |
| PRE-ENGINEERED SYSTEMS CAN BE SHOP DRAWINGS UNDER A |
| SEPARATE PERMIT. |
| |
| FIRE SPRINKLERS 61G15-32.004 DESIGN OF WATER BASED FIRE |
| PROTECTION SYSTEMS. |
| (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| SOURCES. |
| (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| APPLICABLE: (A-M). |
| |
| 2) THE COVERSHEET LIST THE TOTAL UNDER ROOF SQUARE FEET |
| OF THE BUILDING AS 7,675 SQ. FT. THE NEW LAB IN ITSELF |
| IS OVER THE 10% OF THE BUILDING. THE EXISTING LAB WOULD |
| APPEAR TO BE AROUND 600 SQ. FT. OR A TOTAL AREA OF |
| 1,949 SQ. FT. WHICH HAS OR COULD HAVE HAZARDOUS |
| CHEMICALS. PLEASE PROVIDE THE CHEMICALS TO BE USED IN |
| THE LAB AND MSDS SHEETS, AMOUNT OF CHEMICALS THAT ARE |
| TO BE USED IN EACH OF THE LAB AREAS, IF THE CHEMICALS |
| ARE TO BE STORED IN 1 HOUR RATED FIRE CABINETS. THE |
| PLANS FAIL TO SHOW A FIRE SEPARATION (FIRE BARRIERS) |
| FOR CONTROL AREAS FROM THE REMAINDER OF THE BUILDING. |
| |
| 2017 FBC-B 307.1 HIGH-HAZARD GROUP H OCCUPANCY |
| INCLUDES, AMONG OTHERS, THE USE OF A BUILDING OR |
| STRUCTURE, OR A PORTION THEREOF, THAT A PHYSICAL OR |
| HEALTH HAZARD IN QUANTITIES IN EXCESS OF THOSE ALLOWED |
| IN CONTROL AREAS COMPLYING WITH SECTION 414, BASED ON |
| THE MAXIMUM ALLOWABLE QUANTITY LIMITS FOR CONTROL AREAS |
| SET FORTH IN TABLES 307.1(1) AND 307.1(2). |
| PLEASE SEE SECTION 414.2 OF THE 2017 FBC-B FOR CONTROL |
| AREAS. |
| |
| 3) THE SHEET 023-S-2 UNDER THE HEADING OF FOUNDATIONS |
| NOTE # 1 INDICATES THERE IS A SOILS REPORT PREPARED BY |
| FEDERAL ENGINEERING AND TESTING, DATED AUGUST 24, 2018. |
| PLEASE SUBMIT A PAPER ORIGINAL SIGNATURE AND SEALED OR |
| SUBMIT ELECTRONICALLY WITH AN ELECTRONIC SIGNATURE. |
| |
| 4A) PLEASE REVIEW SHEET 023-S-2 THE NEGATIVE VALUES |
| (PRESSURES) FOR VULT AND VASD ARE THE SAME THE VASD |
| VALUES SHOULD BE MULTIPLIED BY THE 0.6 TO BECOME VASD. |
| 2017 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| THE WALL NEGATIVE PRESSURES ALSO APPEAR FOR THE WALL |
| ALSO APPEAR 3.5 LBS. LOW PRESSURES ARE TAKEN AT 15 FEET |
| ABOVE GRADE, THAT IS THE LAST PRESSURE GIVEN IN THE |
| TABLES IN 1609 AND IN ASCE 7-10. |
| |
| 4B) PRESSURES (NEGATIVE) GIVEN ON SHEET 012-A-200 FOR |
| THE WALL ALSO APPEAR 3.5 LBS. LOW PRESSURES ARE TAKEN |
| AT 15 FEET ABOVE GRADE THAT IS THE LAST PRESSURE GIVEN |
| IN THE TABLES IN 1609 AND IN ASCE 7-10. |
| |
| 5) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE AND OR INSULATION, |
| |
| 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| THE SPECIFIC SITE. |
| |
| 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 9) THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE THE |
| ADDITION IS TO HAVE A BAR JOIST AND METAL DECK ROOF |
| SYSTEM. PLEASE HAVE A 3RD PARTY ENGINEER REVIEW ALL |
| WELDED JOINTS AND BOLTED JOINTS AND SUPPLY A SIGNED AND |
| SEALED LETTER OF THE INSPECTIONS AT THE TIME OF THE |
| WINDOW BUCK INSPECTION AND BEFORE THE INTERIOR FRAMING |
| INSPECTION. IF THERE IS ANY QUESTIONS IN REGARDS TO |
| BUILDING INSPECTIONS PLEASE CONTACT THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD AT 561-805-6666. |
| WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| 2017 FBC-B 2204.2 BOLTING. |
| |
| 10) ENERGY CODE. THE APPLICANT HAS SUBMITTED THE ENERGY |
| GAUGE SUMMIT ASHRAE 90.1 ENERGY COST BUDGET OPTION OF |
| CODE COMPLIANCE FOR ENERGY. THE QUESTION THAT I HAVE IS |
| ON THE INPUT DATA REPORT PAGE 2 FOR THE EXTERIOR WALLS |
| THE REPORT SHOWS WIDTH AND HEIGHT (EFFECTIVE) OF THE |
| WALLS. THE QUESTION IS THE HEIGHT OF THE WALL IS GIVEN |
| AT 9 FEET AND ON SHEET A-220 ALL OF THE DETAILS SHOW |
| THE EXTERIOR WALL INSULATION GOING UP TO 9 FEET THE |
| HEIGHT OF THE DROPPED CEILING, WHEREAS THE ROOF TOP |
| INSULATION IS GIVEN AT A HEIGHT OF 12 FOOT 3 INCHES. |
| PLEASE PROVIDE WHY THE EXTERIOR WALL INSULATION OR THE |
| EXTERIOR SOFFIT AND FACIA WOULD NEED TO COMPLETE THE |
| INSULATION TO THE ROOF LINE, TO MAKE A COMPLETE |
| ENVELOPE? |
| |
| 2017 FBC-ENERGY CODE C304.3.2.2 APPLICANT-DETERMINED |
| ASSEMBLY U-FACTORS, C-FACTORS, F-FACTORS OR HEAT |
| CAPACITIES. IF THE BUILDING OFFICIAL DETERMINES THAT |
| THE PROPOSED CONSTRUCTION ASSEMBLY IS NOT ADEQUATELY |
| REPRESENTED IN THE APPROPRIATE TABLE OF ASHRAE 90.1 |
| NORMATIVE APPENDIX A, THE APPLICANT SHALL DETERMINE |
| APPROPRIATE VALUES FOR THE ASSEMBLY USING THE |
| ASSUMPTIONS IN ASHRAE 90.1 NORMATIVE APPENDIX A. |
| |
| 11A) THE ROOF PLAN, SHEETS 011-A-110, 039-P1.2 AND |
| 013-A-220 ALL REPRESENT THE ROOF PLAN. THE SHEET P1.2 |
| DOES GIVE THE ROOF AREA AND PARAPET TO BE DRAINED AND |
| THE SIZE OF THE VERTICAL LEADERS. WHAT IS MISSING IS |
| THE ANNUAL RAIN FALL. SEE 1503.4 ROOF DRAINAGE OF THE |
| 2017 FBC-B. UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF |
| EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS |
| SHALL COMPLY WITH SECTION 1503 AND THE FLORIDA BUILDING |
| CODE, PLUMBING, CHAPTER 11. |
| |
| 11B) PLEASE REVIEW SHEET 011-A-110 THE ROOF PLAN. |
| DETAIL 3 INDICATES THE NEW ROOF LINE IS IN AT A HIGHER |
| ELEVATION THAN THE OLD ROOF. WHEN VIEWING THE EXISTING |
| ROOF LINE IN DETAIL 1 IN THE END VIEW OF THE ROOF IT |
| APPEARS THAT THERE IS 2 EMERGENCY OVERFLOW SCUPPERS |
| THAT WILL BE NO LONGER EFFECTIVE SINCE THE NEW ROOF |
| LINE IS HIGHER? HOW OR WHERE WILL THE EMERGENCY |
| OVERFLOWS BE LOCATED IN THE EXISTING ROOF? |
| |
| 2017 FBC-B 1503.4.1 SECONDARY (EMERGENCY OVERFLOW) |
| DRAINS OR SCUPPERS. WHERE ROOF DRAINS ARE REQUIRED, |
| SECONDARY (EMERGENCY OVERFLOW) ROOF DRAINS OR SCUPPERS |
| SHALL BE PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION |
| EXTENDS ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL |
| BE ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR |
| ANY REASON. THE INSTALLATION AND SIZING OF SECONDARY |
| EMERGENCY OVERFLOW DRAINS, LEADERS AND CONDUCTORS SHALL |
| COMPLY WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF |
| THE FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| |
| 12) SHEET 015-A-401 DETAILS 3 AND 6 . |
| 12A) DETAIL 3 SHOWS EITHER POWER DRIVEN FASTENER OR |
| EXPANSION ANCHOR BEING INSTALLED INTO THE BOTTOM OF AN |
| EXISTING PRE-CAST ROOF JOIST. PLEASE GET THE STRUCTURAL |
| ENGINEER TO SIGN OFF ON THIS APPLICATION SINCE THE |
| BOTTOM REINFORCING MAYBE ENDANGERED OR CONCRETE MAYBE |
| CHIPPED OR CRACKED EXPOSING THE BOTTOM CHORD OF |
| INFORCEMENT. 107.2.1.2 ADDITIONAL DATA. THE BUILDING |
| OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, STRESS |
| DIAGRAMS, AND OTHER DATA NECESSARY TO DESCRIBE THE |
| CONSTRUCTION OR INSTALLATION AND THE BASIS OF |
| CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO |
| BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE |
| AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS |
| STATE LAW REQUIRES. |
| |
| 12B) PLEASE REVIEW DETAIL 6 OF THE SAME SHEET. HIGH HAT |
| IS TO BE APPLIED TO THE CORNER OF AN EXISTING BEAM, THE |
| PLANS SHOW ONE PIECE OF HIGH-HAT FLANGE AT THE CORNER |
| OF THE BEAM THERE IS NO MENTION OF HOW TO ANCHOR THE |
| HIGH HAT AND WHAT DISTANCE TO STAY AWAY FROM THE CORNER |
| TO KEEP FROM THE CONCRETE FROM SPAWLING. . 107.2.1.2 |
| ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE |
| DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA |
| NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION |
| AND THE BASIS OF CALCULATIONS. ALL DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE |
| BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR |
| ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL, |
| SIGNATURE AND DATE AS STATE LAW REQUIRES. |
| |
| 13) THE VALUE OF THE PROJECT WAS REDUCED FROM |
| $1,686,678.00 TO $300,000.00 IN VALUE. PLEASE PROVIDE |
| AN ITEMIZED LIST TO SEE WHAT WAS REMOVED FROM THE |
| PROJECT VALUE, INCLUDE THE LINE ITEM VALUE FOR EACH |
| ITEM REMOVED. |
| 109.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| PRIME OR MASTER PERMIT. |
| |
| 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |