2019-01-25 08:24:15 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| JOSEAN A. DUPREY |
| BUILDING PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6716 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. THERE'S NO RECORD OF ENGINEERED STRUCTURAL |
| ATTACHMENT FOR THIS INSTALLATION. ON PREVIOUS |
| APPLICATION #13100053 IT WAS REQUIRED BUT NOT PROVIDED. |
| 1A. PROVIDE ATTACHMENT TYPE, SIZE AND LOCATION FROM |
| ROOF DECK OR ROOF TRUSSES TO SUPPORT CHANNELS. FBC 107 |
| 1B. PROVIDE INFORMATION ON THE SUBSTRATE TYPE AND |
| FASTENING SCHEDULE TO TRUSSES. FBC 107 |
| 1C. PROVIDE INFORMATION ON WEATHER PROTECTION AND |
| PERFORMANCE REQUIREMENTS. FBC107 |
| |
| 2. PLEASE PROVIDE STRUCTURAL INSTALLATION DETAILS AND |
| CALCULATIONS WITH ORIGINAL SIGNATURE BY THE PERSON |
| RESPONSABLE FOR THE DESIGN. FBC 107 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |