2019-01-02 12:00:30 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18120878 |
| 1/2/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE $3000.00 VALUE LISTED ON THE APPLICATION IS LOW |
| FOR THE INSTALLATION OF A NEW 5-TON AC SYSTEM AND |
| DUCTWORK. PERMIT VALUE IS BASED ON LABOR, MATERIALS, |
| EQUIPMENT, SITE WORK, DESIGN FEES, AND OVER HEAD AND |
| PROFIT PER SECTION 109.3 WPB. PLEASE PROVIDE A CONTRACT |
| AND INVOICES TO VERIFY ACCURATE JOB VALUE. |
| |
| 2) A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY AIR |
| SYSTEM OF THE NEW 5-TON AC SYSTEM PER SECTION 606.2.1 |
| FBC M.. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF |
| THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE |
| NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| |
| 3) THE 500 CFMS OF AIR IN OFFICE 3 DOES NOT APPEAR TO |
| BE CONSISTENT WITH THE AC CALULATIONS WHICH SHOWS THE |
| COOLING LOADS TO BE THE SAME AS OFFICE 2. OFFICE 2 HAS |
| ONLY 150 CFMS OF AIR PROVIDED. |
| |
| 4) ENGINEERED WIND LOAD CALCULATIONS ARE REQUIRED FOR |
| INSTALLATION OF THE ROOFTOP CONDENSER AND STAND- |
| SECTION 301.15 FBC M. IN ADDITION PLEASE SUBMIT A FL. |
| PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE CONDENSER |
| STAND. |
| |
| 5) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.2 |
| FBC M. |
| |
| 6) PROVIDE AN ELECTRICAL PLAN AND AN ELECTRIC |
| SUB-PERMIT- SECTION 107 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |