Plan Review Notes For Permit 18120854 |
Permit Number |
18120854 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-02-13 16:24:07 | MECHANICAL PROVISO: | | | | PROVIDE A REVISED MECHANICAL PLAN THAT INCLUDES: | | | | 1) AIR BALANCE CALCULATION. | | | | 2) AUTOMATIC OPERATION OF THE EXHAUST SYSTEMS WHEN THE | | SPACES ROOMS OR SPACES ARE IN USE. | | | | 3) WIND LOAD ENGINEERING FOR INSTALLATION OF THE | | ROOFTOP EXHAUST VENTILATORS. |
|