Plan Review Notes
Plan Review Notes For Permit 18120854
Permit Number 18120854
Review Stop P
Sequence Number 1
Notes
Date Text
2019-01-17 12:08:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET P-1; SANITARY RISER. CORRECT ON PLAN
 AS NOTED BELOW PER WPB FBC 107.2.1.
 A.2" HUB DRAIN SERVICING THE WATER HEATER
 1) A P-TRAP REQUIRED PER FBC PL 1002.1.
 2) A SEPERATE VENT IS REQUIRED FOR THE TRAPPED FIXTURE
 DRAIN PER FBC PL 901.2.1 AND SECTION 909. LENGTH OF
 FIXTURE DRAIN SHALL COMPLY WITH FBC PL TABLE 909.1.
 PLEASE NOTE THAT THE PROVISIONS OF FBC PL 911 AND 912
 DO NOT APPLY TO THIS INSTALLATION.
 B. LAUNDRY
 1) FIXTURE BRANCH SERVICING THE TWO (2) CLOTHES WASHER
 FIXTURE DRAINS SHALL BE MINIMUM 3" SIZE PER FBC PL
 406.2.
 2) CLOTHES WASHER FIXTURE DRAINS AND TRAPSD SHALL BE
 MINIMUM 2" SIZE PER FBC PL 406.2 AND TABLE 709.1.
 3) UPSTREAM CLOTHES WASHER FIXTURE DRAIN IS S-TRAPPED
 WHICH IS PROHIBITED PER FBC PL 1002.3 (5). SHOW
 COMPLIANCE WITH FBC PL SECTION 909.
 C. SHAMPOO BACKWASH SINKS
 1) IDENTIFY EACH TRAP ON ISOMETRIC AS THE NOTED
 INTERCEPTOR, ZURN Z1175 PER WPB FBC 107.2.1.
  
 2. RE: PLAN SHEET P-1; WATER RISER ISOMETRIC. CORRECT
 ON PLAN AS NOTED BELOW PER WPB FBC 107.2.1.
 A. EXISTING WATER COLD WATER SERVICE/DISTRIBUTION
 APPEARS TO BE COMMON TO THE ENTIRE BUILDING. PROVIDE
 SIZING OF EXISTING COMMON SERVICE/DISTRIBUTION AND
 CALCULATIONS WHICH INCLUDE THE EXISTING USAGE IN THE
 BUILDING PER WPB FBC 107.2.1.
 B. SHOW THE FULL EXTENT OF THE HOT WATER RETURN LINE ON
 THE RISER DIAGRAM SHOWING COMPLIANCE WITH FBC PL 607.2
 PER WPB FBC 107.2.1.
 C. PROVIDE SHUT OFF VALVE FOR SERVICE INTO THE UNIT PER
 FBC 606.1.
  
 3. WATER HEATER
 A. PROVIDE A SCHEMATIC OF THE SPECIFIED BOTTOM FED
 WATER HEATER WITH RECIRC PUMP, EXPANSION TANK AND
 PIPING SHOWING ALL SIZING, VALVING (INCLUDING CHECK
 VALVES AND VACUUM RELIEF VALVE) AND PIPING
 INTERCONNECTIONS PER WPB FBC 107.2.1.
 B. PROVIDE SIZE OF EXPANSION TANK SHOWING COMPLIANCE
 WITH FBC PL 607.3 PER WPB FBC 107.2.1.
  
 4. PROVIDE A FIXTURE SCHEDULE WITH THE FOLLOWING
 INFORMATION PER WPB FBC 107.2.1.
 A. MANUFACTURER NAME AND MODEL # WITH NOTE "EQUAL TO".
 INCLUDE FAUCET FOR LAVATORY AND MOP SINK.INDICATE TYPE
 OF BACKFLOW PREVENTION TO PROVIDE FOR MOP SINK FAUCET.
 1) IF BY OWNER, THEN NOTE IN SCHEDULE. INDICATE THE
 TYPE OF BACKFLOW PREVENTION TO PROVIDE WHERE APPLICABLE
 IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL SECTION
 608. PLEASE NOTE THAT SUBMITTAL DATA FOR OWNER SUPPLIED
 EQUIPMENT COVERED UNDER THE PLUMBING SCOPE WILL HAVE TO
 BE SUBMITTED TO THE BUILDING DEPARTMENT AND APPROVED
 AND IN PLACE ON THE JOBSITE PRIOR TO FINAL INSPECTION.
 B. WATER USAGE OF FIXTURE
 C. ADA COMPLIANCE FOR THE WATER CLOSET, LAVATORY AND
 ELECTRIC WATER COOLER IN ACCORDANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6.
  
 5. PER WPB FBC 107.2.1, PROVIDE SCHEDULE AND SPEC FOR
 WATER HEATER AND RECIRC PUMP; INCLUDE ELECTRICAL
 CHARACTERISTICS OF THE EQUIPMENT.
  
 6. IS EXISTING TOILET ROOM ADA COMPLIANT? IF SO, THEN
 STATE ON THE PLANS AND SHOW TURNING RADIUS FOR
 WHEELCHAIR PER WPB FBC 107.2.1.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715