2018-12-28 11:20:26 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. BATHROOM RECEPTACLE CIRCUITS D2-25 AND D2-30 ARE |
| SHOWN AS 15 AMP. A MINIMUM OF ONE 20 AMPERE BRANCH |
| CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| 2. THERE IS A CONFLICT BETWEEN THE RISER DIAGRAM AND |
| THE PANEL SCHEDULES. RISER SHOWS ONE PANEL WITH TWO |
| SECTIONS. PANEL SCHEDULES SHOW TWO DIFFERENT PANELS, |
| ONE WITH A 250 AMP MAIN BREAKER AND ONE WITH A 100 AMP |
| MAIN BREAKER. IS PANEL D3 FEED FROM PANEL D2? CLARIFY |
| AND CORRECT. IF TWO PANELS, SHOW FEEDER SIZE TO EACH |
| AND WHERE FEED FROM. WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |