Plan Review Notes
Plan Review Notes For Permit 18120844
Permit Number 18120844
Review Stop E
Sequence Number 1
Notes
Date Text
2018-12-28 11:20:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BATHROOM RECEPTACLE CIRCUITS D2-25 AND D2-30 ARE
 SHOWN AS 15 AMP. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 2. THERE IS A CONFLICT BETWEEN THE RISER DIAGRAM AND
 THE PANEL SCHEDULES. RISER SHOWS ONE PANEL WITH TWO
 SECTIONS. PANEL SCHEDULES SHOW TWO DIFFERENT PANELS,
 ONE WITH A 250 AMP MAIN BREAKER AND ONE WITH A 100 AMP
 MAIN BREAKER. IS PANEL D3 FEED FROM PANEL D2? CLARIFY
 AND CORRECT. IF TWO PANELS, SHOW FEEDER SIZE TO EACH
 AND WHERE FEED FROM. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  