2019-01-15 16:08:28 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW: |
| PLUMBING COMMENTS: DENIED |
| |
| 1. RE: PLAN SHEET 5 OF 7; PLUMBING RISER DIAGRAM |
| A. PER FBC RES P3108.1, "EACH WET VENTED FIXTURE DRAIN |
| SHALL CONNECT DIRECTLY TO THE HORIZONTAL WET VENT." IN |
| THE CASE OF THE MASTER BATH, THE TUB DRAIN AND WATER |
| CLOSET DRAIN SHALL NOT CONNECT TO EACHG OTHER BEFORE |
| CONNECTING TO THE VENT. |
| B. PER FBC RES P3104.4 AND 3104.5 THE DRY VENT SHALL |
| RISE VERTICALLY ABOVE THE FLOOD LEVEL RIM OF HIGHEST |
| TRAPPED FIXTURE BEING VENTED BEFORE OFFSETTING AND |
| CONNECTING TO ANOTHER VENT. THE LAVATORY IN THE IN BATH |
| #2 DOES NOT COMPLY. |
| C. PER WPB FBC 107.2.1, INCLUDE THE WASTE AND VENT |
| PIPING FOR THE HALF BATH ON THE PLUMBING RISER DIAGRAM. |
| D. PER FBC P2717.2 SINK AND DISHWASHER, THE COMBINED |
| DISCHARGE FROM A DISHWASHER AND A ONE- OR |
| TWO-COMPARTMENT SINK, WITH OR WITHOUT A FOOD-WASTE |
| DISPOSER, SHALL BE SERVED BY A TRAP OF NOT LESS THAN |
| 11/2 INCHES (38 MM) IN OUTSIDE DIAMETER. THE DISHWASHER |
| DISCHARGE PIPE OR TUBING SHALL RISE TO THE UNDERSIDE OF |
| THE COUNTER AND BE FASTENED OR OTHERWISE HELD IN THAT |
| POSITION BEFORE CONNECTING TO THE HEAD OF THE |
| FOOD-WASTE DISPOSER OR TO A WYE FITTING IN THE SINK |
| TAILPIECE |
| 2. PER WPB FBC 107.2.1, ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. |
| |