Plan Review Notes For Permit 18120823
Permit Number 18120823
Review Stop M
Sequence Number 1
Notes
Date Text
2019-01-04 09:22:21MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED RETURN AIR IN MASTER BEDROOM PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL M1602.3 BALANCED RETURN
 AIR.
  
 2- CANNOT TAKE RETURN AIR FROM CLOSET PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL M1602.2 RETURN AIR
 OPENINGS.
  