2019-01-24 08:25:50 
 3RD REVIEW: 18120818
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.SHT. A0.1 DETAIL #1-2 GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE AS THEY ARE SHOWN NOW THERE IS 2
 DIFFERENT DIMENSIONS DETAIL #2 IS NOT CODE COMPLIANT .
 FBC ACC 609.4
  
 2. SHT. A0.1 PLEASE SHOW COMPLIANCE WITH FBC ACC 606.3
 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 3. SHT. A1.1 PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 TOILET AND LAVATORY WITH DIMENSIONS. PER FBC ACC
 604.3.1, 606.2
  
 4. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.3
 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 5. SHT. P-1 THE LAVATORY'S ON THE SANITARY ISOMETRIC
 ARE S TRAPPED WHICH IS PROHIBITED THEY SHALL HAVE A
 VENT STACK OR AAV. PER FBC PL 1002.3, 901.2.1
  
 6. SHT. P-1 ON THE SANITARY ISOMETRIC THE BREAK ROOM
 SINK APPEARS TO BE LABELED AS A LAVATORY PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  