2019-01-14 14:22:33 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE SIZE OF EXISTING METER CAN, AND METHOD TO |
| TAP ADDITIONAL PANEL FEEDERS, PROVIDE CORRECTED RISER |
| DIAGRAM SHOWING WIRE SIZES TO EACH LOCATION. NEC 215.5, |
| 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; WPB FBC 107.2.1 |
| 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| 3. RISER DIAGRAM SHOWS A 200 AMP FEED TO A 100 AMP |
| PANEL, WHICH LOAD CALCULATION STATES HAS A DEMAND LOAD |
| OF 111 AMPS. THIS SAME PANEL ON PLAN IS SHOWN AS A 150 |
| AMP PANEL. THE PANEL CANNOT BE SMALLER THAN THE |
| CAPACITY OF THE FEEDERS AND OCP. PROVIDE CORRECTION. |
| NEC 408.30, 408.36; FBC RE E3706.1, E3706.3 |
| 4. THE RSIER DIAGRAM SHOWS 2/0 WIRE FOR THE 200 AMP |
| FEEDERS. THIS WIRE SIZE IS NOT RATED FOR 200 AMPS. WIRE |
| SIZES FROM NEC 310.15(B)(7), OR FBC RE E3603.1, CAN |
| ONLY BE USED WHEN THE SERVICE CONDUCTOR SUPPLIES 100% |
| OF THE LOAD. SINCE THIS IS NOT THE CASE, PROVIDE |
| CORRECTED WIRE SIZE FROM METER CAN TO PANELS. NEC |
| 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1 |
| 5. THE RISER SHOWS THE GROUNDING OF THE SYSTEM |
| ESTABLISHED AT THE SERVICE. AN ADDITIONAL GROUNDING |
| ELECTRODE AND GROUNDING ELECTRODE CONDUCTOR SHOULD NOT |
| BE INSTALLED AT THE NEW SUB-PANEL. PROVIDE CORRECTION. |
| NEC 250.6; FBC RE E3610.4 |
| 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3606.3 |
| 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |