2019-01-14 14:22:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SIZE OF EXISTING METER CAN, AND METHOD TO
 TAP ADDITIONAL PANEL FEEDERS, PROVIDE CORRECTED RISER
 DIAGRAM SHOWING WIRE SIZES TO EACH LOCATION. NEC 215.5,
 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 3. RISER DIAGRAM SHOWS A 200 AMP FEED TO A 100 AMP
 PANEL, WHICH LOAD CALCULATION STATES HAS A DEMAND LOAD
 OF 111 AMPS. THIS SAME PANEL ON PLAN IS SHOWN AS A 150
 AMP PANEL. THE PANEL CANNOT BE SMALLER THAN THE
 CAPACITY OF THE FEEDERS AND OCP. PROVIDE CORRECTION.
 NEC 408.30, 408.36; FBC RE E3706.1, E3706.3
 4. THE RSIER DIAGRAM SHOWS 2/0 WIRE FOR THE 200 AMP
 FEEDERS. THIS WIRE SIZE IS NOT RATED FOR 200 AMPS. WIRE
 SIZES FROM NEC 310.15(B)(7), OR FBC RE E3603.1, CAN
 ONLY BE USED WHEN THE SERVICE CONDUCTOR SUPPLIES 100%
 OF THE LOAD. SINCE THIS IS NOT THE CASE, PROVIDE
 CORRECTED WIRE SIZE FROM METER CAN TO PANELS. NEC
 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1
 5. THE RISER SHOWS THE GROUNDING OF THE SYSTEM
 ESTABLISHED AT THE SERVICE. AN ADDITIONAL GROUNDING
 ELECTRODE AND GROUNDING ELECTRODE CONDUCTOR SHOULD NOT
 BE INSTALLED AT THE NEW SUB-PANEL. PROVIDE CORRECTION.
 NEC 250.6; FBC RE E3610.4
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  