2019-01-29 14:58:35 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| FBC R 401.3 (DRAINAGE) |
| FBC 107.2.5 (SITE PLAN) |
| FBC 110.9 (IMPACT OF CONSTRUCTION) |
| |
| 2- THE PROPOSED STRUCTURE IS LOCATED IN FLOOD ZONE AE |
| WITH BASE FLOOD ELEVATIONS 7. ACCORDING TO CITY |
| ORDINANCE 4729-17 SEC. 18-34 THE FINISH FLOOR ELEVATION |
| NEEDS TO BE TWO FEET ABOVE THE BASE FLOOD ELEVATION. |
| THE FINISH FLOOR OF THE PROPOSED ADDITION NEEDS TO |
| COMPLY AND THE EXISTING HOUSE FINISHED FLOOR AND ALL |
| EQUIPMENT NEEDS TO BE RAISED IF THERE IS NOT A 2 FEET |
| FREEBOARD. PROVIDE SURVEY SHOWING THE EXISTING HOUSE |
| FINISHED FLOOR. |
| |
| 3- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. 1106 FBC-EXISTING BUILDING. |
| |
| 4- DETAIL SECTION 11/6.2 KEYED ON SECOND FLOOR FRAMING |
| PLAN ON SHEET 4.1 IS NOT SHOWN ON SHEET 6.2. |
| CONSTRUCTION IN THIS AREA IS NOT CLEAR. IT'S NOT CLEAR |
| IF THE SECOND FLOOR WALL IN THIS AREA IS CONCRETE BLOCK |
| OR WOOD FRAMED. SECOND FLOOR FRAMING PLANS INDICATES |
| CONCRETE BLOCK, WHILE SECOND FLOOR PLAN ON SHEET 3.2 |
| INDICATES WOOD FRAMED WALL. REVISE FLOORS PLANS TO |
| MATCH PROPOSED CONSTRUCTION. PROVIDE COMPLETE 11/6.2 |
| WALL SECTION. SPECIFY ALL FRAMING MEMBERS AND |
| CONNECTORS. IF WOOD FRAMED WALL, THEN ALSO SPECIFY |
| CONNECTIONS AT THE SUPPORTING ENDS OF THE FLOOR GIRDER |
| SPECIFIED ON SHEET 4.1 SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 5- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS |
| BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". |
| REVISE THE DESIGN PARAMETER INFORMATION ON SHEET 3.1 |
| AND ALL THE DESIGN PRESSURES SHOWN ON SHEET 5.1. |
| NOTE: ALL PRODUCT APPROVALS WILL BE REVIEWED ONCE |
| DESIGN PRESSURES ARE REVISED. |
| |
| 6- ENGINEER TO CLEARLY SPECIFY ALL LIVE AND DEAD LOADS |
| ON THE SECOND FLOOR. SEE TABLE R301.5 FBC-RESIDENTIAL |
| FOR MINIMUM DESIGN LOADS. |
| |
| 7- ENGINEER TO CLEARLY SPECIFY ALL THE LIVE AND DEAD |
| LOADS ON THE ROOF TRUSSES. CLEARLY SPECIFY THE TOP AND |
| BOTTOM CHORDS LIVE AND DEAD LOADS (INCLUDING ATTIC LIVE |
| LOAD). SEE NOTES "B" AND "G" OF TABLE R301.5 |
| FBC-RESIDENTIAL. |
| |
| 8- NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS |
| REQUIRED BY TABLE R702.1(1). |
| |
| 9- NEED TO SPECIFY TWO WATER RESISTIVE BARRIERS WHEN |
| STUCCO IS APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3 |
| FBC-RESIDENTIAL. |
| |
| 10- SURVEY, SITE PLAN AND PROJECT LOCATION MAP ON SHEET |
| C.1 SHOW A ROOF STRUCTURE ON THE REAR OF THE HOUSE |
| WHICH EXTENDS UP TO THE REAR PROPERTY LINE. THERE ARE |
| NO CITY RECORDS FOR THE CONSTRUCTION OF THIS STRUCTURE. |
| NEED TO OBTAIN PERMIT OR REMOVE STRUCTURE. SEC. 105.1 |
| CITY AMENDMENTS. |
| |
| 11- SHEET 3.1: |
| A) DESIGN PARAMETERS SPECIFIES CONSTRUCTION TYPE IIIB |
| FOR THIS BUILDING. THIS BUILDING DOESN'T SEEM TO COMPLY |
| WITH ALL THE REQUIREMENTS OF TYPE IIIB CONSTRUCTION AS |
| REQUIRED BY SEC. 602.3 FBC. IT LOOKS MORE LIKE |
| CONSTRUCTION TYPE VB. REVISE AS REQUIRED OR PROVIDE |
| FULL COMPLIANCE WITH SPECIFIED TYPE OF CONSTRUCTION. |
| |
| B)WINDOWS ON EXISTING BEDROOM #4 DON'T COMPLY WITH THE |
| EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING |
| BUILDING. NOTE: THIS BEDROOM HAD FRENCH DOOR LEADING TO |
| THE OUTSIDE BUT THEY WERE REMOVED TO ALLOW FOR THE |
| ADDITION. THEREFORE NEED TO PROVIDE WINDOWS THAT |
| PROVIDE THE MINIMUM OPENINGS REQUIRED BY SEC. R310.2 |
| FBC-RESIDENTIAL. REVISE WINDOW SCHEDULE ACCORDINGLY. |
| |
| C) WINDOW SCHEDULE INDICATES THAT WINDOW "B" IS AN |
| EGRESS WINDOW. 52 1/8" X 37 5/8" SINGLE HUNG WINDOW |
| DOESN'T COMPLY AS AN EGRESS WINDOW. REVISE AS REQUIRED. |
| CLEARLY SPECIFY ROUGH OPENING SIZE OF EXISTING WINDOWS |
| ON BEDROOM #1 AND BEDROOM #2. AND, EXISTING TYPE AND |
| SIZE OF THESE WINDOWS TO VERIFY COMPLIANCE WITH THE |
| REQUIREMENTS OF SEC. 702.5 FBC-EXISTING BUILDING. |
| |
| D) SPECIFY WHAT IS THE USE OF THE ROOM ADJACENT TO THE |
| EXISTING FAMILY ROOM AREA. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| E) TYPE AND SIZE OF EXTERIOR DOOR SHOWN ON THE FAMILY |
| ROOM DOESN'T MATCH DOOR SHOWN ON THE NORTH ELEVATION ON |
| SHEET 5.1. REVISE AS REQUIRED TO MATCH. REVISE DOOR |
| SCHEDULE ALSO. SEC. 107.2.1 CITY AMENDMENTS. NOTE: SAME |
| THING APPLIES TO WINDOW SHOWN ON THE ROOM ADJACENT TO |
| THE FAMILY ROOM. |
| |
| 12- SHEET 3.2: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ROOF |
| DRAINAGE AT NEW TERRACE SHOWING COMPLIANCE WITH SEC. |
| R903.4 FBC-RESIDENTIAL. SPECIFY ROOF DRAINS AND |
| OVERFLOW SCUPPERS. ALSO, REVISE THE ROOF SLOPE. MIN |
| SLOPE IS 1/4" PER FOOT NOT 1/8 PER FOOT. |
| |
| B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| TERRACE WATERPROOFING AND FINISH FLOORING. SEC. R903.1 |
| FBC-RESIDENTIAL. |
| |
| 13- SHEET 4.2: |
| A) SPECIFICATIONS ON THE PLYWOOD SHEATHING NAILING |
| SCHEDULE DON'T MATCH SPECIFICATIONS SHOWN ON ROOF |
| SHEATHING DETAIL ON SHEET 5.2. REVISE AS REQUIRED TO |
| MATCH. NOTE: SEC. R803.2.3.1 FBC-RESIDENTIAL REQUIRES |
| 8D RING SHANK NAILS MIN. |
| |
| B) REVISE ROOF ZONES SHOWN ON THE GABLE PLAN. ACCORDING |
| TO FIGURE R803.2.3.1 FBC-RESIDENTIAL WHOLE GABLE END IS |
| CONSIDERED ROOF ZONE 3. ALSO, THE MINIMUM DIMENSION "A" |
| FOR GABLE ENDS IS 5'-0" NOT 3'-0". REVISE AS REQUIRED. |
| |
| C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE HAND FRAMED OVERHANG SPECIFIED AT |
| THE GABLE ENDS ON THE ROOF FRAMING PLAN. SPECIFY |
| FRAMING MEMBERS AND CONNECTORS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 14- SHEET 5.2: |
| MASTER BEDROOM WINDOWS (WINDOW "G" PER WINDOW SCHEDULE) |
| SHOWN ON THE WEST ELEVATION NEED TO HAVE E WINDOW FALL |
| PROTECTION AS REQUIRED BY SEC. R312.2 FBC-RESIDENTIAL. |
| SHOW COMPLIANCE. |
| |
| 15- SOIL TEST REPORT SUBMITTED NEEDS TO HAVE THE |
| ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY |
| CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORDS. |
| |
| 16- ICYNENE FOAM INSULATION INFORMATION WAS SUBMITTED. |
| PLANS DON'T SPECIFY ICYNENE FOAM INSULATION OR ANY |
| OTHER FOAM INSULATION. ACTUALLY PLANS CALL FOR |
| VENTILATED ATTIC AND R-30 BATT INSULATION. NEED TO |
| EITHER REVISE PLANS SHOWING A DESIGN FOR UNVENTED ATTIC |
| AND SPECIFYING THE FOAM INSULATION OR OMIT THE ICYNENE |
| INSULATION. NOTE: COORDINATE WITH REQUIRED ENERGY |
| CALCULATIONS TO AVOID CONFLICTS/DELAYS. SEC. R103.2 |
| FBC-ENERGY CONSERVATION. |
| |
| 17- SPECIFY CARBON MONOXIDE ALARM WITHIN ALL SLEEPING |
| ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC. |
| R315.1 FBC-RESIDENTIAL. |
| |
| 18- NEED TO PROVIDE MECHANICAL VENTILATION TO EXISTING |
| BATHROOM AT BEDROOM #4, AND EXISTING BATHROOM #1 |
| BECAUSE THE WINDOWS WERE REMOVED. SEC. R303.3 |
| FBC-RESIDENTIAL. |
| |
| 19- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR |
| REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW |
| COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |