Plan Review Notes
Plan Review Notes For Permit 18120801
Permit Number 18120801
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-11 17:22:34****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
  
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. MISSING INFORMATION FOR THE TUBE STEEL BEAM
  CONNECTIONS AT ROOF EXPANSION JOINTS FOUND ON PAGES
  (CEA 161) AND (CES 101). (COMPLIED)
  
 2. WE NEED TO REVIEW/AUDIT THE APPROVED STEEL SHOP
 DRAWINGS. (NOT COMPLIED, PLEASE SUBMIT STEEL SHOP
 DRAWINGS)
  
 3. WE NEED AN APPROVED CLARIFICATION THAT THE WIND LOAD
  DESIGN (RISK CATEGORY 2) AS INDICATED ON PAGE (CES
 001)
  IS ACCURATE. IT APPEARS THAT THIS MAY ACTUALLY BE A
  RISK CATEGORY 3. (COMPLIED)
  
 4. WE NEED TO REVIEW/AUDIT THE STEEL ERECTORS WELD
  PROCEDURE SPECIFICATIONS AS PER THE FBC B REFERENCED
  STANDARDS AND THE REQUIREMENTS INDICATED ON PAGE (CES
 004) REFERENCING THE AMERICAN WELDING SOCIETY. (NOT
 COMPLIED, PLEASE SUBMIT THE WELD PROCEDURE
 SPECIFICATIONS)
  
  
  
  PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
  RESULT IN NEW PLAN REVIEW COMMENTS.
  