2019-02-15 14:18:03 | ELECTRICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. OVERCURRENT PROTECTION FOR NEW TANKLESS WATER HEATER | | SHALL BE LIMITED TO 50 AMPS. PANEL SCHEDULE SHOWS 60 | | AMP BREAKER. | | 2. CANNOT VERIFY OVERCURRENT PROTECTION FOR NEW A/C | | CONDENSOR. PROVIDE MANUF. SPECS. | | | | | | |
|