2019-07-17 15:28:044TH REVIEW 181207744
  
  
 PREVIOUS COMMENT NOT COMPLIED WITH:
  
 2) THE RESPONSE NARRATIVE TO COMMENT #2 OF THE REVIEW
 DONE ON 4/23/19 STATES THAT THE GUTTER DESIGN IS A DECK
 LEVEL PERIMETER OVERFLOW GUTTER. PERIMETER OVERFLOW
 GUTTERS SHALL COMPLY WITH 2017 FBC-BUILDING
 SEC.454.1.6.5.3.1 FOR SPACING REQUIREMENTS. SHT.
 SP-1.05 SHOWS THE SPACING OF THE DRAINS.
 A SIGNED AND SEALED LETTER FROM THE ENGINEER SHOWING
 HOW IT IS HYDRAULICALLY JUSTIFIED THAT THE DRAIN
 SPACING ON THE OVERFLOW GUTTER EXCEEDS WHAT IS
 PERMITTED BY CODE. THE PLAN SHOW 20' BETWEEN DRAINS THE
 CODE STATES THE MAXIMUM IS 15'
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER