Plan Review Notes
Plan Review Notes For Permit 18120744
Permit Number 18120744
Review Stop P
Sequence Number 3
Notes
Date Text
2019-06-18 12:16:201) PLACE THE SPECIFIC ADDRESS OF THIS PROJECT ON
 SHT.SP-1.00. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE RESPONSE NARRATIVE TO COMMENT #2 OF THE REVIEW
 DONE ON 4/23/19 STATES THAT THE GUTTER DESIGN IS A DECK
 LEVEL PERIMETER OVERFLOW GUTTER. PERIMETER OVERFLOW
 GUTTERS SHALL COMPLY WITH 2017 FBC-BUILDING
 SEC.454.1.6.5.3.1 FOR SPACING REQUIREMENTS. SHT.
 SP-1.05 SHOWS THE SPACING OF THE DRAINS.
 3) PLACE THE CORRECT ADDRESS ON THE POOL SUBMITTAL
 INFORMATION PACKAGE. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SPECIFICATIONS HAVE BEEN SUBMITTED FOR BRINE TANKS
 BUT I DO NOT SEE THE TANKS ON THE PLANS NOR LISTED IN
 ANY EQUIPMENT SCHEDULE. CLARIFY.
 A SEPARATE PERMIT WILL BE REQUIRED FOR THE INSTALLATION
 OF THE GAS POOL HEATER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW