Date |
Text |
2019-04-23 05:43:14 | 1) SUBMIT MANUFACTURER'S DETAILS/SPECIFICATIONS FOR THE |
| POOL SHOWER. THE RESPONSE NARRATIVE STATES THAT THE |
| SHOWER INFORMATION HAS BEEN ELIMINATED AND TO REFER TO |
| THE MASTER PERMIT FOR THE SHOWER DETAIL.I COULD NOT |
| FIND ANY DETAIL FOR THE SHOWER IN THE MASTER PLANS. |
| THERE IS STILL ONE MANUFACTURER'S SPECIFICATION SHEET |
| INCLUDED IN THIS SUBMITTAL BUT IT DOES NOT PROVIDE THE |
| REQUIRED INFORMATION REQUESTED FROM THE FIRST REVIEW. |
| 2ND REQUEST. |
| 2) THE SPACING OF THE GUTTER DRAINS SHALL COMPLY WITH |
| 2017 FBC - BUILDING SEC. 454.1.6.5.3.1. 2ND REQUEST. |
| 3) THE PLANS REFER TO THE DISCHARGE OF RAINWATER TO THE |
| SANITARY SYSTEM (SHT.SP-1.05) AND THE POOL MAINTENANCE |
| LINE TO THE SANITARY.STORMWATER AND THE POOL MAINTENACE |
| LIONE CANNOT DRAIN TO THE SANITARY SYSTEM PER CITY |
| ORDINANCE ARTICLE III, SEC.90-126 (B) (5). PLEASE |
| CONTACT MANNY GONZALEZIN THE CITY OF WEST PALM BEACH |
| ENGINEERING DEPT. FOR FURTHER DIRECTION. HE CAN BE |
| REACHED AT 561-494-1040. |
| 4) PLACE THE CALCULATIONS FOR THE CARTRIDGE FILTRATION |
| RATE ON THE POOL PLANS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 5) PLACE THE SPECIFIC ADDRESS OF THIS PROJECT ON ALL OF |
| THE PLAN SHEETS AND ON THE PERMIT APPLICATION. SEE PLAN |
| SHEETS SP-1.01, SP-1.03, E-4.0.0, AND E-5.0.1. 2ND |
| REQUEST. |
| 6) SHT.SP-2.04 - LEVEL 5 SWIMMING POOL LEGEND - NOTE |
| "H" - REFERS TO THE DISCHARGE OF THE POOL MAINTENANCE |
| LINE TO THE STORM DRAINAGE SYSTEM. CITY ORDINANCE |
| CHAPTER 90, ARTICLE V, SEC. 90-203 ( A) ONLY PERMITS |
| STORMWATER TO BE DISCHARGED INTO THE STORMWATER SYSTEM. |
| ALSO, THERE IS A NOTE ON THE POOL EQUIPMENT ROOM PIPING |
| PLAN THAT THE 4 INCH MAINTENANCE DRAIN LINE IS TO |
| DISCHARGE TO THE SANITARY SEWER. THIS IS NOT PERMITTED |
| PER CITY ORDINANCE CHAPTER 90, ARTICLE III, SEC.90-126 |
| (B) (5). PLEASE CONTACT MANNY GONZALEZ IN THE CITY OF |
| WEST PALM BEACH ENGINEERING DEPT. FOR FURTHER |
| DIRECTION. HE CAN BE REACHED AT 561-494-1040. 2ND |
| REQUEST. |
| 7) A SEPARATE GAS PERMIT WILL BE REQUIRED FOR THE |
| INSTALLATION OF THE GAS POOL HEATER. THE MASTER SET OF |
| PLANS HAS A NOTE STATING " POOL HEATER BY OTHERS." |
| MANUFACTURER'S SPECIFICATIONS FOR THE POOL HEATER ALONG |
| WITH DETAILS SHOWING THE TYPE OF VENT, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| DETAILS OF THE GAS VENT AND COMBUSTION AIR CALCULATIONS |
| SHALL BE SUBMITTED ALONG WITH THE GAS PERMMIT |
| APPLICATION.2017 FBC-FUEL GAS SECS. 502 THRU 505. WPB |
| AMEND. TO FBC SEC. 105.1. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |
| |