2019-02-25 14:49:081) SHT. SP- 1.02 - A NOTE IN THE LOWER RIGHT HAND
 CORNER OF THE PLAN REFERS TO THE 2014 FLORIDA BUILDING.
 REVISE THE NOTE TO READ THE 2017 FLORIDA BUILDING CODE.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MDF
 SHOWER TOWER. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHOW THE WIDTH OF THE POOL ON THE PLANS.THE
 DIMENSIONS ARE MISSING ON THE RIGHT SIDE OF THE POOL ON
 SHT. SP- 1.04.WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. SP-1.05 - SHOW THE SPACING OF THE GUTTER DRAINS
 ON THE PLANS. SPACING SHALL CCOMPLY WITH 2017 FBC
 SEC.454.1.6.5.3.1.
 5) SHT. SP-1.05 - SIZE THE GUTTER LINE TO THE COLLECTOR
 TANK.
 6) SHT. SP-1.05 - SIZE THE RETURN LINE BRANCES INTO THE
 POOL.
 7) SHT. SP-1.07 - DETAIL #10 CALLS OUT THE MAXIMUM FLOW
 FOR THE PARAMOUNT MAIN DRAIN AT 95 GPM @1.5 FPS AND THE
 MAIN DRAIN TABLE IN THE DETAIL SHOWS THE SAME PARAMOUNT
 DRAIN WITH A FLOW OF 200 GPM. CLARIFY.
 8) SHT. SP-1.07 - THE MAIN DRAIN TABLE REFERS TO
 FLORIDA BUILDING CODE SEC. 424.1. THIS CODE SECTION IS
 FOR CHILDREN'S PLAY STRUCTURES AND IS OBVIOUSLY
 INCORRECT. REVISE THE NOTE WITH THE CORRECT CODE
 SECTION.
 9) THE PLANS REFER TO THE DISCHARGE OF RAINWATER TO THE
 SANITARY ( SHT. SP-1.05) AND THE POOL MAINTENANCE LINE
 TO THE SANIRAY. STORMWATER AND THE POOL MAINTENACE LIN
 CANNOT DRAIN TO THE SANITARY SYSTEM PER CITY ORDINANCE
 ARTICLE III, SEC. 90-126 (B) (5). PLEASE CONTACT MANNY
 GONZALEZ IN THE CITY OF WEST PALM BEACH ENGINEERING
 DEPT. FOR FURTHER DIRECTION. 561-494-.1040.
 10) SHT. SP-1.08 - DETAIL # 1 - PLACE A NOTE ON THIS
 SHEET THAT THE LEGEND FOR THE SHOWN ITEMS IS LOCATED ON
 SHT. SP-2.04. WPB AMEND. TO FBC SEC. 107.2.1.
 11) SUBMIT VERIFICATION THAT THE MAXIMUM FILTRATION
 RATE IN GALLONS PER MINUTE PER SQUARE FOOT OF FILTER
 AREA OF 0.375 FOR CARTRIDGE FILTERS IS NOT EXCEEDED PER
 2017 FBC SEC.454.1.6.5.5.1
 12) SHT. SP-1.08 - THE PLANS REFER TO NSF-50, 2007. THE
 REFERENCED EDITION IN THE FBC IS THE 2011 EDITION.
 PLEASE REVISE THE NOTE.
 13) SHT. SP-1.08 - THE POOL HEATER SHALL HAVE A MINIMUM
 THERMAL EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY,
 TABLE C404.2.
 14) SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505.
 15) PLACE THE SPECIFIC ADDRESS OF THIS PROJECT ON ALL
 PLAN SHEETS AND THE APPLICATION.FL. STATUTE 713.135.
 16) SHT. SP-1.08 - DETAIL #6 - THE PLANS READ" SEE MEP
 PLANS FOR FLUE TERMINATION." WHAT MEP PLANS? CLARIFY.
 17) ALL HOSE BIBBS SHALL BE EQUIPPED WITH A SEPARATE
 SHUTOFF VALVE PER 2017 FBC-PLUMBING SEC. 606.2.
 18) SHT. SP-2.04 - LEVEL 5 SWIMMING POOL LEGEND - NOTES
 "F" & "H" - REFER TO THE DISCHARGE OF RAINWATER AND THE
 POOL MAINTENANCE LINE TO THE SANITARY SEWER. STORMWATER
 AND THE POOL MAINTENACE LIN CANNOT DRAIN TO THE
 SANITARY SYSTEM PER CITY ORDINANCE ARTICLE III, SEC.
 90-126 (B) (5). PLEASE CONTACT MANNY GONZALEZ IN THE
 CITY OF WEST PALM BEACH ENGINEERING DEPT. FOR FURTHER
 DIRECTION. 561-494-.1040.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  