2019-02-25 14:49:08 | 1) SHT. SP- 1.02 - A NOTE IN THE LOWER RIGHT HAND |
| CORNER OF THE PLAN REFERS TO THE 2014 FLORIDA BUILDING. |
| REVISE THE NOTE TO READ THE 2017 FLORIDA BUILDING CODE. |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MDF |
| SHOWER TOWER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 3) SHOW THE WIDTH OF THE POOL ON THE PLANS.THE |
| DIMENSIONS ARE MISSING ON THE RIGHT SIDE OF THE POOL ON |
| SHT. SP- 1.04.WPB AMEND. TO FBC SEC. 107.2.1. |
| 4) SHT. SP-1.05 - SHOW THE SPACING OF THE GUTTER DRAINS |
| ON THE PLANS. SPACING SHALL CCOMPLY WITH 2017 FBC |
| SEC.454.1.6.5.3.1. |
| 5) SHT. SP-1.05 - SIZE THE GUTTER LINE TO THE COLLECTOR |
| TANK. |
| 6) SHT. SP-1.05 - SIZE THE RETURN LINE BRANCES INTO THE |
| POOL. |
| 7) SHT. SP-1.07 - DETAIL #10 CALLS OUT THE MAXIMUM FLOW |
| FOR THE PARAMOUNT MAIN DRAIN AT 95 GPM @1.5 FPS AND THE |
| MAIN DRAIN TABLE IN THE DETAIL SHOWS THE SAME PARAMOUNT |
| DRAIN WITH A FLOW OF 200 GPM. CLARIFY. |
| 8) SHT. SP-1.07 - THE MAIN DRAIN TABLE REFERS TO |
| FLORIDA BUILDING CODE SEC. 424.1. THIS CODE SECTION IS |
| FOR CHILDREN'S PLAY STRUCTURES AND IS OBVIOUSLY |
| INCORRECT. REVISE THE NOTE WITH THE CORRECT CODE |
| SECTION. |
| 9) THE PLANS REFER TO THE DISCHARGE OF RAINWATER TO THE |
| SANITARY ( SHT. SP-1.05) AND THE POOL MAINTENANCE LINE |
| TO THE SANIRAY. STORMWATER AND THE POOL MAINTENACE LIN |
| CANNOT DRAIN TO THE SANITARY SYSTEM PER CITY ORDINANCE |
| ARTICLE III, SEC. 90-126 (B) (5). PLEASE CONTACT MANNY |
| GONZALEZ IN THE CITY OF WEST PALM BEACH ENGINEERING |
| DEPT. FOR FURTHER DIRECTION. 561-494-.1040. |
| 10) SHT. SP-1.08 - DETAIL # 1 - PLACE A NOTE ON THIS |
| SHEET THAT THE LEGEND FOR THE SHOWN ITEMS IS LOCATED ON |
| SHT. SP-2.04. WPB AMEND. TO FBC SEC. 107.2.1. |
| 11) SUBMIT VERIFICATION THAT THE MAXIMUM FILTRATION |
| RATE IN GALLONS PER MINUTE PER SQUARE FOOT OF FILTER |
| AREA OF 0.375 FOR CARTRIDGE FILTERS IS NOT EXCEEDED PER |
| 2017 FBC SEC.454.1.6.5.5.1 |
| 12) SHT. SP-1.08 - THE PLANS REFER TO NSF-50, 2007. THE |
| REFERENCED EDITION IN THE FBC IS THE 2011 EDITION. |
| PLEASE REVISE THE NOTE. |
| 13) SHT. SP-1.08 - THE POOL HEATER SHALL HAVE A MINIMUM |
| THERMAL EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY, |
| TABLE C404.2. |
| 14) SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF |
| VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| 2017 FBC-FUEL GAS SECS. 502 THRU 505. |
| 15) PLACE THE SPECIFIC ADDRESS OF THIS PROJECT ON ALL |
| PLAN SHEETS AND THE APPLICATION.FL. STATUTE 713.135. |
| 16) SHT. SP-1.08 - DETAIL #6 - THE PLANS READ" SEE MEP |
| PLANS FOR FLUE TERMINATION." WHAT MEP PLANS? CLARIFY. |
| 17) ALL HOSE BIBBS SHALL BE EQUIPPED WITH A SEPARATE |
| SHUTOFF VALVE PER 2017 FBC-PLUMBING SEC. 606.2. |
| 18) SHT. SP-2.04 - LEVEL 5 SWIMMING POOL LEGEND - NOTES |
| "F" & "H" - REFER TO THE DISCHARGE OF RAINWATER AND THE |
| POOL MAINTENANCE LINE TO THE SANITARY SEWER. STORMWATER |
| AND THE POOL MAINTENACE LIN CANNOT DRAIN TO THE |
| SANITARY SYSTEM PER CITY ORDINANCE ARTICLE III, SEC. |
| 90-126 (B) (5). PLEASE CONTACT MANNY GONZALEZ IN THE |
| CITY OF WEST PALM BEACH ENGINEERING DEPT. FOR FURTHER |
| DIRECTION. 561-494-.1040. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |