2019-01-16 10:49:52 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK. |
| THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| CONTRACTOR WOULD PROVIDE. |
| YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| RENTAL TO VERIFY VALUE. |
| |
| CITY OF WPB CHPT. 1 ? VALUE |
| 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION |
| COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| BUILDING OFFICIAL. |
| |
| YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| RENTAL TO VERIFY VALUE. |
| |
| 2. IMPACT FEES MAY BE REQUIRED. |
| |
| PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE |
| PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS |
| APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF. |
| |
| 3. NEW INTERIOR WALLS IN BEDROOM #1 ARE NOT INCLUDED IN |
| DESCRIPTION OF WORK ON PERMIT APPLICATION. IF THIS WORK |
| IS TO BE INCORPORATED INTO THIS PERMIT, INCLUDE THE SOW |
| ON APPLICATION. |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 4. SLAB REPAIR DETAIL ON PLAN PAGE D-1 IS LACKING |
| TRANSFER DOWELS FROM NEW TO EXISTING. DESIGNER TO |
| PROVIDE DETAIL. |
| |
| 5. INTERIOR WALL AT FIREPLACE APPEARS TO CHANGE TYPE OF |
| CONSTRUCTION FROM THE EXISTING PLAN TO THE PROPOSED |
| PLAN. PLEASE CLARIFY WHAT IS CHANGING AT THIS WALL |
| SECTION. |
| |
| 6. GLAZING AT BATHTUB SHALL CONFORM THE FBC R308. |
| |
| R308.4.5 GLAZING AND WET SURFACES. |
| GLAZING IN WALLS, ENCLOSURES OR FENCES CONTAINING OR |
| FACING HOT TUBS, SPAS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, |
| BATHTUBS, SHOWERS AND INDOOR OR OUTDOOR SWIMMING POOLS |
| WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS |
| THAN 60 INCHES (1524 MM) MEASURED VERTICALLY ABOVE ANY |
| STANDING OR WALKING SURFACE SHALL BE CONSIDERED TO BE A |
| HAZARDOUS LOCATION. THIS SHALL APPLY TO SINGLE GLAZING |
| AND EACH PANE IN MULTIPLE GLAZING. |
| EXCEPTION: GLAZING THAT IS MORE THAN 60 INCHES (1524 |
| MM), MEASURED HORIZONTALLY AND IN A STRAIGHT LINE, FROM |
| THE WATER?S EDGE OF A BATHTUB, HOT TUB, SPA, WHIRLPOOL |
| OR SWIMMING POOL OR FROM THE EDGE OF A SHOWER, SAUNA OR |
| STEAM ROOM. |
| |
| 7. PROVIDE PRODUCT APPROVALS FOR NEW DOOR AT STUDY. |
| |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE DOOR SUBMITTALS. |
| |
| 8. LANDING AT NEW DOOR AT STUDY SHALL COMPLY WITH R311. |
| |
| R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE |
| LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE |
| DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE |
| PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT |
| VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). |
| R311.3.2 FLOOR ELEVATIONS FOR OTHER EXTERIOR DOORS. |
| DOORS OTHER THAN THE REQUIRED EGRESS DOOR SHALL BE |
| PROVIDED WITH LANDINGS OR FLOORS NOT MORE THAN 73/4 |
| INCHES (196 MM) BELOW THE TOP OF THE THRESHOLD. |
| |
| 9. PROVIDE FOUNDATION DETAIL FOR FLOOR JOIST PIERS. |
| |
| 10. PROVIDE UNDER FLOOR VENTILATION PER R408. |
| |
| R408.2 OPENINGS FOR UNDER-FLOOR VENTILATION. |
| THE MINIMUM NET AREA OF VENTILATION OPENINGS SHALL BE |
| NOT LESS THAN 1 SQUARE FOOT (0.0929 M2) FOR EACH 150 |
| SQUARE FEET (14 M2) OF UNDER-FLOOR AREA. ONE |
| VENTILATION OPENING SHALL BE WITHIN 3 FEET (915 MM) OF |
| EACH CORNER OF THE BUILDING. VENTILATION OPENINGS SHALL |
| BE COVERED FOR THEIR HEIGHT AND WIDTH WITH ANY OF THE |
| FOLLOWING MATERIALS PROVIDED THAT THE LEAST DIMENSION |
| OF THE COVERING SHALL NOT EXCEED 1/4 INCH (6.4 MM): |
| 1. 1.PERFORATED SHEET METAL PLATES NOT LESS THAN 0.070 |
| INCH (1.8 MM) THICK. |
| 2. 2.EXPANDED SHEET METAL PLATES NOT LESS THAN 0.047 |
| INCH (1.2 MM) THICK. |
| 3. 3.CAST-IRON GRILL OR GRATING. |
| 4. 4.EXTRUDED LOAD-BEARING BRICK VENTS. |
| 5. 5.HARDWARE CLOTH OF 0.035 INCH (0.89 MM) WIRE OR |
| HEAVIER. |
| 6. 6.CORROSION-RESISTANT WIRE MESH, WITH THE LEAST |
| DIMENSION BEING 1/8 INCH (3.2 MM) THICK. |
| EXCEPTION: THE TOTAL AREA OF VENTILATION OPENINGS SHALL |
| BE PERMITTED TO BE REDUCED TO 1/1,500 OF THE |
| UNDER-FLOOR AREA WHERE THE GROUND SURFACE IS COVERED |
| WITH AN APPROVED CLASS I VAPOR RETARDER MATERIAL AND |
| THE REQUIRED OPENINGS ARE PLACED TO PROVIDE CROSS |
| VENTILATION OF THE SPACE. THE INSTALLATION OF OPERABLE |
| LOUVERS SHALL NOT BE PROHIBITED. |
| |
| R408.3 UNVENTED CRAWL SPACE. |
| VENTILATION OPENINGS IN UNDER-FLOOR SPACES SPECIFIED IN |
| SECTIONS R408.1 AND R408.2 SHALL NOT BE REQUIRED WHERE |
| THE FOLLOWING ITEMS ARE PROVIDED: |
| 7. EXPOSED EARTH IS COVERED WITH A CONTINUOUS CLASS I |
| VAPOR RETARDER. JOINTS OF THE VAPOR RETARDER SHALL |
| OVERLAP BY 6 INCHES (152 MM) AND SHALL BE SEALED OR |
| TAPED. THE EDGES OF THE VAPOR RETARDER SHALL EXTEND NOT |
| LESS THAN 6 INCHES (152 MM) UP THE STEM WALL AND SHALL |
| BE ATTACHED AND SEALED TO THE STEM WALL OR INSULATION. |
| 8. 2.ONE OF THE FOLLOWING IS PROVIDED FOR THE |
| UNDER-FLOOR SPACE: |
| 1. CONTINUOUSLY OPERATED MECHANICAL EXHAUST VENTILATION |
| AT A RATE EQUAL TO 1 CUBIC FOOT PER MINUTE (0.47 L/S) |
| FOR EACH 50 SQUARE FEET (4.7 M2) OF CRAWL SPACE FLOOR |
| AREA, INCLUDING AN AIR PATHWAY TO THE COMMON AREA (SUCH |
| AS A DUCT OR TRANSFER GRILLE), AND PERIMETER WALLS |
| INSULATED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| ENERGY CONSERVATION. |
| 2. CONDITIONED AIR SUPPLY SIZED TO DELIVER AT A RATE |
| EQUAL TO 1 CUBIC FOOT PER MINUTE (0.47 L/S) FOR EACH 50 |
| SQUARE FEET (4.7 M2) OF UNDER-FLOOR AREA, INCLUDING A |
| RETURN AIR PATHWAY TO THE COMMON AREA (SUCH AS A DUCT |
| OR TRANSFER GRILLE), AND PERIMETER WALLS INSULATED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, ENERGY |
| CONSERVATION. |
| 3. PLENUM IN EXISTING STRUCTURES COMPLYING WITH SECTION |
| M1601.5, IF UNDER-FLOOR SPACE IS USED AS A PLENUM. |
| |
| R408.4 ACCESS. |
| ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR SPACES. |
| ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF |
| 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS |
| THROUGH A PERIMETER WALL SHALL BE NOT LESS THAN 16 |
| INCHES BY 24 INCHES (407 MM BY 610 MM). WHERE ANY |
| PORTION OF THE THROUGH-WALL ACCESS IS BELOW GRADE, AN |
| AREAWAY NOT LESS THAN 16 INCHES BY 24 INCHES (407 MM BY |
| 610 MM) SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY |
| SHALL BE BELOW THE THRESHOLD OF THE ACCESS OPENING. |
| THROUGH WALL ACCESS OPENINGS SHALL NOT BE LOCATED UNDER |
| A DOOR TO THE RESIDENCE. SEE SECTION M1305.1.4 FOR |
| ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| LOCATED UNDER FLOORS. |
| |
| 11. PROVIDE SITE DRAINAGE PLAN. |
| |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. |
| |
| FBC R401.3 SITE DRAINAGE |
| PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING |
| COMPLIANCE WITH FBC R401.3 DRAINAGE. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES WITHIN THE FIRST 10 FEET. |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10 |
| FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE |
| DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING |
| FOUNDATION SHALL BE SLOPED A MINIMUM OF |
| 2 PERCENT AWAY FROM THE BUILDING. |
| |
| FBC R 401.3 (DRAINAGE) |
| FBC 107.2.5 (SITE PLAN) |
| FBC 110.9 (IMPACT OF CONSTRUCTION) |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |
| |