2019-01-07 10:53:12PLAN DENIED
 1) PLEASE SHOW DUCT WORK ON AIR CONDITIONING PLAN
 SHOWING DUCT SIZE AND OUTSIDE AIR DUCT AND SIZE.
 2) NEW CONFERENCE ROOM SHOWS THREE SUPPLY DROPS
 AND ONE RETURN. REFER TO SECTION 601.6 BALANCED RETURN
 AIR
 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER