2019-12-10 14:06:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
 1. SECOND REQUEST: WATER DISPENSER/TAG R15 ON PLAN
 SHEET A2.0. A BACKFLOW PREVENTION DEVICE IS REQUIRED ON
 THE POTABLE WATER SUPPLY IN ORDER TO COMPLY WITH FBC PL
 608.3. SPECIFY TYPE OF DEVICE AND INDICATE ON WATER
 RISER. SEE COMMENT 1(B) ON REVIEW 1 DATED 1/15/19 AND
 COMMENT 1 ON REVIEW 2, 4/18/19.
 2. ADDITIONAL COMMENT: WATER DISPENSER/TAG R15
 (WATERLOGIC WL800 MAX II) ON PLAN SHEET A2.0. PROVIDE
 INDIRECT WASTE FOR DRAIN(S) FROM MEMBRANE FILTER #2 AND
 HOT AND COLD WATER TANK DRAINS TO A TRAPPED AND VENTED
 WASTE RECEPTACLE THROUGH AN AIR GAP PER FBC PL 802.2.
 INDICATE ON SANITARY RISER. PER WPB FBC 107.2.1, SUBMIT
 THE WL800 OPERATING, INSTALLATION AND SERVICE MANUAL HT
 TPS://WWW.WATERLOGIC.COM/EN-US/MEDIA/USA/RESOURCES/WL80
 0OPERATINGMANUAL.PDF
 3. SECOND REQUEST: HAND SINK/TAG R19-SINK ON PLAN SHEET
 A2.0; PER FBC ACC 804.3.2 AND 606.3, THE WORK SURFACE
 AND FIXTURE RIM SHALL BE 34 INCHES (865 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. ARCHITECT DID NOT
 RESPOND TO REQUEST FOR SINK SPECIFICATION; A SINK AND
 FAUCET SHALL BE SUBMITTED SHOWING COMPLIANCE WITH FBC
 ACC 308, 309 AND 606. ADDITIONALLY, THE INTERIOR
 ELEVATIONS ON A2.0 INDICATE 3'-0" TO TOP OF
 CABINET/SINK RIM.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 18120669 1009 BANYAN BLVD
  
  
  
  