2019-12-10 14:06:31 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 3RD REVIEW |
| PLUMBING COMMENTS: DENIED |
| 1. SECOND REQUEST: WATER DISPENSER/TAG R15 ON PLAN |
| SHEET A2.0. A BACKFLOW PREVENTION DEVICE IS REQUIRED ON |
| THE POTABLE WATER SUPPLY IN ORDER TO COMPLY WITH FBC PL |
| 608.3. SPECIFY TYPE OF DEVICE AND INDICATE ON WATER |
| RISER. SEE COMMENT 1(B) ON REVIEW 1 DATED 1/15/19 AND |
| COMMENT 1 ON REVIEW 2, 4/18/19. |
| 2. ADDITIONAL COMMENT: WATER DISPENSER/TAG R15 |
| (WATERLOGIC WL800 MAX II) ON PLAN SHEET A2.0. PROVIDE |
| INDIRECT WASTE FOR DRAIN(S) FROM MEMBRANE FILTER #2 AND |
| HOT AND COLD WATER TANK DRAINS TO A TRAPPED AND VENTED |
| WASTE RECEPTACLE THROUGH AN AIR GAP PER FBC PL 802.2. |
| INDICATE ON SANITARY RISER. PER WPB FBC 107.2.1, SUBMIT |
| THE WL800 OPERATING, INSTALLATION AND SERVICE MANUAL HT |
| TPS://WWW.WATERLOGIC.COM/EN-US/MEDIA/USA/RESOURCES/WL80 |
| 0OPERATINGMANUAL.PDF |
| 3. SECOND REQUEST: HAND SINK/TAG R19-SINK ON PLAN SHEET |
| A2.0; PER FBC ACC 804.3.2 AND 606.3, THE WORK SURFACE |
| AND FIXTURE RIM SHALL BE 34 INCHES (865 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. ARCHITECT DID NOT |
| RESPOND TO REQUEST FOR SINK SPECIFICATION; A SINK AND |
| FAUCET SHALL BE SUBMITTED SHOWING COMPLIANCE WITH FBC |
| ACC 308, 309 AND 606. ADDITIONALLY, THE INTERIOR |
| ELEVATIONS ON A2.0 INDICATE 3'-0" TO TOP OF |
| CABINET/SINK RIM. |
| |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| DESIGNER PER WPB FBC 107.2.1. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 18120669 1009 BANYAN BLVD |
| |
| |
| |
| |