Date |
Text |
2019-12-19 10:41:25 | ALTERATION/CHANGE OF OCCUPANCY, THIRD BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| |
| 1- THRU 3. OK |
| |
| 4- WATER TREATMENT PLANT ADMINISTRATION BUILDING |
| -CHEMICAL CONTAINMENT AREAS ENGINEERING SUBMITTED FROM |
| DARREL J. GRAZIANI, P.E : |
| NOTES 1 THRU 3 STATES THAT THE WATER PLANT WILL |
| INITIATE OPERATIONAL CONTROLS TO LIMIT STORAGE OF |
| GALLONS IN THE CONTAINMENT AREAS UNTIL MODIFICATIONS TO |
| THE CONTAINMENT AREAS CAN BE DESIGNED, PERMITTED AND |
| INSTALLED. PLEASE PROVIDE LETTER FROM WATER TREATMENT |
| PLANT DIRECTOR ACKNOWLEDGING THAT THE OPERATING |
| CONTROLS SPECIFIED BY THE ENGINEER WILL BE INITIATED. |
| THIS LETTER OF ACKNOWLEDGMENT IS REQUESTED FOR CITY |
| FILE TO MAKE SURE THE QUANTITIES OF THE HAZARDOUS |
| MATERIALS IN THE CONTAINMENT AREAS WILL NOT EXCEED THE |
| QUANTITIES STATED BY THE ENGINEER OF RECORD AND TABLE |
| 307.1(2) FBC-BUILDING. OTHERWISE, THE BUILDING WILL BE |
| CONSIDERED HIGH HAZARD GROUP H-4 AND MIXED OCCUPANCIES |
| WILL NOT ALLOWED AND ADDITIONAL REQUIREMENTS WILL |
| APPLY. |
| |
| |
| 5- THRU 10. OK |
| |
| 11- REPEAT COMMENT. REVISE THE STRUCTURAL DESIGN |
| CRITERIA & CODES INFORMATION ON SHEET A4.0. |
| (A) THIS IS AN ESSENTIAL FACILITY, THEN THE ULTIMATE |
| DESIGN WIND SPEED IS 180 NOT 170. SEE FIGURE 1609.3(2) |
| FBC AND CITY AMENDMENTS SEC. 120 CITY AMENDMENTS. NOTE: |
| THIS BUILDING IS IN EXPOSURE D NOT C. REVISE AS |
| REQUIRED. |
| |
| (B) REVISE THE DOORS DESIGN PRESSURES TO CORRESPOND TO |
| THE REVISION REQUIRED ABOVE. |
| |
| (C) REVISE THE REFERENCED ASCE-7. THE CORRECT REFERENCE |
| IS THE ASCE 7-10 NOT ASCE 7-16. REVISE AS REQUIRED. |
| |
| 12- REPEAT COMMENT. ALL EXIT DOORS NEED TO HAVE PANIC |
| HARDWARE AS REQUIRED BY SEC. 1010.1.10 FBC. REVISE DOOR |
| HARDWARE SCHEDULE AS REQUIRED (INCLUDING THE EXISTING |
| DOOR E1). THERE ARE NOT SPECIFICATIONS FOR PANIC |
| HARDWARE ON EXISTING DOOR E1. PLEAE PROVIDE |
| INFORMATION. |
| |
| 13- 16 OK |
| |
| 17- WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |