2019-05-06 18:48:10 | ALTERATION/CHANGE OF OCCUPANCY, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- OK |
| |
| 2- OK |
| |
| 3- OK. |
| |
| 4- OCCUPANCY LOADS ON SHEET A0 INDICATES OCCUPANCY |
| FACTORY (F) AND CONFERENCE AREA. CLEARLY SPECIFY TYPE |
| OF FACTORY. F1 OR F2. SEE SEC. 306 FBC. |
| |
| RESPONSE: |
| REVISED OCCUPANCY STATES: |
| MAIN OCCUPANCY: FACTORY GROUP F-1 (ORIGINAL |
| DESIGNATION). |
| ACCESSORY USES: B-BUSINESS; USED ON 2ND LEVEL. |
| S- STORAGE: USED ON 1ST LEVEL |
| A-1 NEW ASSEMBLY USE (CONFERENCE ROOM). |
| |
| NEW ACCESSORY OCCUPANCY LOAD: CONFERENCE AREA 1/15 X |
| +/-836SF=56 OCCUPANTS. |
| |
| THE OCCUPANCY OF THIS BUILDING NEEDS TO BE |
| REVISED/CLARIFIED. |
| (A)ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 |
| PERCENT OF THE FLOOR AREA OF THE STORY IN WHICH THEY |
| ARE LOCATED. SEE SEC. 508.2.3 FBC-BUILDING AND REVISE |
| AS REQUIRED. |
| ALSO, ASSEMBLY IS NOT AN ACCESSORY FOR STORAGE. THIS IS |
| A SEPARATE OCCUPANCY GROUP. SEE SEC. 302.1 |
| FBC-BUILDING. USE |
| |
| (B) BASED ON REVISED FLOOR PLANS ON SHEET A1.0 THE |
| FIRST FLOOR MAY NOT BE CLASSIFIED AS STORAGE . IT MAY |
| BE CLASSIFIED AS HIGH-HAZARD GROUP H. SEE SEC. 307.1 |
| FBC-BUILDING. |
| PROVIDE THE MSDS SHEETS FOR ALL CHEMICALS AND ALL |
| QUANTITIES TO VERIFY IF QUANTITIES ARE IN EXCESS OF |
| THOSE ALLOWED IN CONTROL AREAS. (SEE SEC. 414.2 FOR |
| CONTROL AREAS REQUIREMENTS). |
| NOTE: IF HIGH HAZARD GROUP H IS DETERMINED, THEN MIXED |
| OCCUPANCIES ARE NOT ALLOWED AND ADDITIONAL REQUIREMENTS |
| MAY APPLY. |
| |
| (C)CONFERENCE ROOM IS NOT ASSEMBLY A-1. SINCE THERE IS |
| NOT SPECIFIC ASSEMBLY FOR A CONFERENCE ROOM, THEN IT |
| FALLS MORE IN THE ASSEMBLY GROUP A-3. SEE SEC. 303.4 |
| FBC-BUILDING AND REVISE AS REQUIRED. |
| |
| |
| 5- OK |
| |
| 6- A)FACTORY USE AND ASSEMBLY USE ARE MIXED |
| OCCUPANCIES. SEE 2017 FBC-B 508.1. EACH PORTION OF A |
| BUILDING SHALL BE INDIVIDUALLY CLASSIFIED IN ACCORDANCE |
| WITH SECTION 302.1. WHERE A BUILDING CONTAINS MORE THAN |
| ONE OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF |
| SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION |
| 508.2, 508.3 OR 508.4, OR A COMBINATION OF THESE |
| SECTIONS. |
| |
| B) CLARIFY WHY COVER SHEET AND TITLE BLOCK ON ALL PLANS |
| INDICATE THAT THIS IS "ADMINISTRATION BLDG. CONFERENCE |
| ROOM". THIS BUILDING DOESN'T SEEM TO BE THE |
| ADMINISTRATION BUILDING. IS THERE A FACTORY IN THE |
| ADMINISTRATION BUILDING?. COORDINATE WITH ITEM ABOVE |
| AND REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| COORDINATE WITH ITEM #4 ABOVE. |
| |
| 7- THE DESIGNER OF RECORD WILL ALSO NEED TO INDICATE IF |
| THE NEW CONFERENCE ROOM WILL MEET WHICH SECTION OF THE |
| 2017 FBC-B CODE: |
| 2017 FBC-EXIT. BLDG. CODE 1012.1.1.1 CHANGE OF |
| OCCUPANCY CLASSIFICATION WITHOUT SEPARATION |
| 2017 FBC-EXIT. BLDG. CODE 1012.1.1.2 CHANGE OF |
| OCCUPANCY CLASSIFICATION WITH SEPARATION. |
| |
| RESPONSE: |
| (A)COORDINATE WITH ITEM #4 ABOVE. |
| |
| (B) IF THE OCCUPANCY SEPARATION IS ALLOWED, THEN THE |
| REQUIRED SEPARATION SHALL BE FIRE BARRIERS. NEED TO |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| APPROVED FIRE BARRIER WALL AND APPROVED HORIZONTAL FIRE |
| RATED ASSEMBLY AS REQUIRED BY SEC. 508.4.4.1 |
| FBC-BUILDING. |
| NOTE: EXISTING CONCRETE BLOCK WALL DOESN'T NECESSARILY |
| MAKES A TWO HOUR FIRE RATED WALL. NEED TO PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS FOR TYPE OF |
| CONCRETE BLOCK USED ON THE WALL TO VERIFY THAT IT MEETS |
| THE FIRE RATING STATED. SAME APPLIES TO THE EXISTING |
| FLOOR /CEILING ASSEMBLY. |
| |
| 8- OK. |
| |
| 9- 2017 FBC-EXIT. BLDG. CODE 1012.1.4 ACCESSIBILITY. |
| ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8. |
| EXIST. BLDG. CODE. 1012.8 ACCESSIBILITY EXISTING |
| BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE |
| FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |
| A) PLEASE SHOW HOW COMPLIANCE WITH SEC. 202.4 FLORIDA |
| ACCESSIBILITY CODE ( 2012 EDITION). SHOW PATH OF TRAVEL |
| TO THE ALTERED AREA, INCLUDING THE RESTROOMS, ETC. SEE |
| SEC. 202.4 FAC. |
| |
| RESPONSE: |
| CLARIFY WHAT IS THE ACCESSIBLE ROUTE TO ENTER THE NEW |
| CONFERENCE ROOM. ONLY THRU THE CORRIDOR DOOR OR ALSO |
| THRU THE NEW EXTERIOR DOUBLE DOORS. PLANS DON'T SHOW |
| ANY INFORMATION OF THE DOORS THRESHOLD. ARE THE NEW |
| EXTERIOR DOORS PART OF THE ACCESSIBLE ROUTE TO THE NEW |
| CONFERENCE ROOM? I APOLOGIZE, I SHOULD OF CLARIFY AND |
| ASK FOR THE ACCESSIBLE ROUTE TO ENTER THE NEW |
| CONFERENCE ROOM. SEE SEC. 206.2.1 FBC-ACCESSIBILITY. |
| |
| |
| B) FLOOR PLAN SHOWS WHAT APPEARS TO BE A SINK AND |
| CABINETRY MAYBE A BREAK AREA. THE PLANS DO NOT SHOW |
| COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE SECTION 606 |
| SINKS. |
| 606.2 CLEAR FLOOR SPACE. |
| 606.3HEIGHT. |
| 606.4 FAUCETS. |
| 606.5 EXPOSED PIPES AND SURFACES. |
| |
| RESPONSE: |
| SINK HEIGHT DOESN'T COMPLY WITH SEC. 606.3. |
| THERE IS NOT INFORMATION FOR EXPOSED PIPES AND SURFACE |
| PROTECTION AS REQUIRED BY SEC. 606.5. |
| |
| 10- OK. |
| |
| 11- PROVIDE COMPLETE WIND DESIGN DATA AS REQUIRED BY |
| SEC. 1603.1.4 FBC. |
| NOTE: CHECK TABLE 1604.5 FBC. THIS BUILDING LOOKS LIKE |
| IS ESSENTIAL FACILITY. AND REVISE EXTERIOR DOORS DESIGN |
| PRESSURES SHOWN ON SHEET A4.0. |
| |
| RESPONSE: |
| REVISE THE STRUCTURAL DESIGN CRITERIA & CODES |
| INFORMATION ON SHEET A4.0. |
| (A) ASCE REFERENCED IN THE 2017 FBC IS THE ASCE 7-10 |
| NOT ASCE 7-16. REVISE AS REQUIRED. |
| |
| (B) IF THIS IS AN ESSENTIAL FACILITY, THEN THE ULTIMATE |
| DESIGN WIND SPEED IS 180 NOT 170. SEE FIGURE 1609.3(2) |
| FBC AND CITY AMENDMENTS SEC. 120 CITY AMENDMENTS. NOTE: |
| THIS BUILDING IS IN EXPOSURE D NOT C. REVISE AS |
| REQUIRED. |
| |
| (C) REVISE THE DOORS DESIGN PRESSURES TO CORRESPOND TO |
| THE REVISION REQUIRED ABOVE. |
| |
| 12- ALL EXIT DOORS NEED TO HAVE PANIC HARDWARE AS |
| REQUIRED BY SEC. 1010.1.10 FBC. REVISE DOOR HARDWARE |
| SCHEDULE AS REQUIRED (INCLUDING THE EXISTING DOOR E1). |
| |
| RESPONSE: |
| THERE ARE NOT SPECIFICATIONS FOR PANIC HARDWARE ON |
| EXISTING DOOR E1. |
| |
| 13- OK |
| |
| 14- OK |
| |
| 15- OK |
| |
| 16 VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS |
| TO BE LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON |
| PLANS. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. REVISE AS REQUIRED OR PROVIDE COPIES OF |
| SIGNED CONTRACTS FOR BUILDING OFFICIAL APPROVAL. |
| |
| 17- WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |
| |