2019-01-15 09:48:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET A2.0; KITCHENETTE
 A. TAG R19-SINK: SINK SHALL COMPLY WITH THE
 REQUIREMENTS OF FBC ACC SECTION 606 PER FBC ACC 212.3;
 PLANS SHALL PROVIDE THE APPROPRIATE INFORMATION SHOWING
 COMPLIANCE PER WPB FBC 107.2.1.PROVIDE SPECIFICATION
 FOR SINK PER WPB FBC 107.2.1.
 B. TAG R15-WATER DISPENSER: ON PLUMBING PLAN SHEET
 P1.1, THERE IS NO PROVISION FOR WATER SUPPLY TO THE
 WATER DISPENSER OR WASTE. PROVIDE THE APPROPRIATE
 INFORMATION ON THE PLANS, INCLUDING ANY REQUIREMENTS
 FOR BACKFLOW PREVENTION AS OUTLINED IN FBC PL SECTION
 608 AND PROVIDE SPECIFICATION FOR WATER DISPENSER PER
 WPB FBC 107.2.1.
 2. RE: PLAN SHEET P1.1; DETAIL #1 SPECIFIES 3/4" HOT
 WATER TO FIXTURES AND RISER #2 SPECIFIES 1/2" HOT
 WATER. PLEASE CLARIFY PER WPB FBC 107.2.1
 3. RE: PLAN SHEET A0; THE RENOVATION IS TAKING PLACE IN
 A 12,000+ SQ FT FACILITY FACTORY (F) OCCUPANCY. THE
 EXISTING PLUMBING COUNT NOTES BATHROOM FIXTURES AND THE
 EXISTING BATHROOMS ARE LOCATED ON PLAN SHEET D1 FLOOR
 PLANS;THERE IS NO INDICATION OF A SERVICE SINK OR A
 DRINKING FOUNTAIN AS REQUIRED BY FPC PL TABLE 403.1.
 P:LEASE CLARIFY PER WPB FBC 107.2.1.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  