Plan Review Notes
Plan Review Notes For Permit 18120669
Permit Number 18120669
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-10 12:34:19ALTERATION/CHANGE OF OCCUPANCY, BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- UNDER THE 2017 FBC-EXISTING BUILDING CODE, THE
 DESIGNER OF RECORD HAS NOT LISTED WHICH METHOD THE
 PLANS WERE CREATED. 2017 FBC-EXISTING BUILDING CODE
 SECTION 301.1. THE ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER. PLEASE NOTE FOR THIS
 ROOM IT IS CONSIDERED A CHANGE OF OCCUPANCY.
  
 2- THERE ARE MANY BUILDINGS IN THIS PROPERTY. PROVIDE
 PLOT PLAN SHOWING LOCATION OF BUILDING WHERE WORK IS
 TAKEN PLACE. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- REVISE PROJECT DATA INFORMATION ON SHEET A0: THIS IS
 NOT ALTERATION LEVEL II. THIS IS CHANGE OF OCCUPANCY.
 SEC. 506 FBC-EXISTING BUILDING.
 APPLICABLE SECTIONS OF CHAPTER 10 WILL APPLY. REVISE AS
 REQUIRED.
  
 4- OCCUPANCY LOADS ON SHEET A0 INDICATES OCCUPANCY
 FACTORY (F) AND CONFERENCE AREA. CLEARLY SPECIFY TYPE
 OF FACTORY. F1 OR F2. SEE SEC. 306 FBC.
  
 5- PROJECT DATA ON SHEET AO DOESN'T SPECIFY IF THIS
 BUILDING IS SPRINKLERED OR NOT. SEC. 107.3.5.1 CITY
 AMENDMENTS.
  
 6- A)FACTORY USE AND ASSEMBLY USE ARE MIXED
 OCCUPANCIES. SEE 2017 FBC-B 508.1. EACH PORTION OF A
 BUILDING SHALL BE INDIVIDUALLY CLASSIFIED IN ACCORDANCE
 WITH SECTION 302.1. WHERE A BUILDING CONTAINS MORE THAN
 ONE OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 508.2, 508.3 OR 508.4, OR A COMBINATION OF THESE
 SECTIONS.
  
 B) CLARIFY WHY COVER SHEET AND TITLE BLOCK ON ALL PLANS
 INDICATE THAT THIS IS "ADMINISTRATION BLDG. CONFERENCE
 ROOM". THIS BUILDING DOESN'T SEEM TO BE THE
 ADMINISTRATION BUILDING. IS THERE A FACTORY IN THE
 ADMINISTRATION BUILDING?. COORDINATE WITH ITEM ABOVE
 AND REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- THE DESIGNER OF RECORD WILL ALSO NEED TO INDICATE IF
 THE NEW CONFERENCE ROOM WILL MEET WHICH SECTION OF THE
 2017 FBC-B CODE:
 2017 FBC-EXIT. BLDG. CODE 1012.1.1.1 CHANGE OF
 OCCUPANCY CLASSIFICATION WITHOUT SEPARATION
 2017 FBC-EXIT. BLDG. CODE 1012.1.1.2 CHANGE OF
 OCCUPANCY CLASSIFICATION WITH SEPARATION.
  
 8- RENOVATED FLOOR PLAN SHOWS TWO SINGLE IN-SWING DOORS
 INTO THE CONFERENCE ROOM FROM THE INTERIOR EXIT ACCESS
 CORRIDOR. PLEASE SHOW COMPLIANCE WITH:
 2017 FBC-B SECTION 1010.1.2.1 DIRECTION OF SWING. PIVOT
 OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 9- 2017 FBC-EXIT. BLDG. CODE 1012.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8.
 EXIST. BLDG. CODE. 1012.8 ACCESSIBILITY EXISTING
 BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 A) PLEASE SHOW HOW COMPLIANCE WITH SEC. 202.4 FLORIDA
 ACCESSIBILITY CODE ( 2012 EDITION). SHOW PATH OF TRAVEL
 TO THE ALTERED AREA, INCLUDING THE RESTROOMS, ETC. SEE
 SEC. 202.4 FAC.
  
 B) FLOOR PLAN SHOWS WHAT APPEARS TO BE A SINK AND
 CABINETRY MAYBE A BREAK AREA. THE PLANS DO NOT SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE SECTION 606
 SINKS.
 606.2 CLEAR FLOOR SPACE.
 606.3HEIGHT.
 606.4 FAUCETS.
 606.5 EXPOSED PIPES AND SURFACES.
  
 10- BUILDING THERMAL ENVELOPE. IT IS NOT CLEAR IF
 BUILDING IS AIR CONDITIONED OR NOT.
 A) DESIGNER OF RECORD TO REPRESENT THE BUILDING'S
 THERMAL ENVELOPE ON PLANS AS REQUIRED BY SEC. C103.2.1
 FBC-ENERGY CONSERVATION.
 NOTE: SEE BUILDING THERMAL ENVELOPE DEFINITION ON
 CHAPTER 2 OF FBC.
  
 B) PROVIDE COMPLETE INFORMATION ON PLANS INCLUDING BUT
 NOT LIMITED TO INSULATION R VALUES ON ALL WALLS,
 CEILING, ETC. AS REQUIRED BY SEC. C103.2 FBC-ENERGY
 CONSERVATION.
  
 C) ENERGY FORM SUBMITTED IS MISSING THE BUILDING
 ENVELOPE INFORMATION. AND, DESIGNER OF RECORD TO SIGN
 AND PROVIDE PROFESSIONAL REGISTRATION NUMBER ON THE
 ENERGY CODE FORM AS REQUIRED BY SEC. C103.1.1.1.2
 FBC-ENERGY CONSERVATION.
  
 11- PROVIDE COMPLETE WIND DESIGN DATA AS REQUIRED BY
 SEC. 1603.1.4 FBC.
 NOTE: CHECK TABLE 1604.5 FBC. THIS BUILDING LOOKS LIKE
 IS ESSENTIAL FACILITY. AND REVISE EXTERIOR DOORS DESIGN
 PRESSURES SHOWN ON SHEET A4.0.
  
 12- ALL EXIT DOORS NEED TO HAVE PANIC HARDWARE AS
 REQUIRED BY SEC. 1010.1.10 FBC. REVISE DOOR HARDWARE
 SCHEDULE AS REQUIRED (INCLUDING THE EXISTING DOOR E1).
  
 13-DETAIL 1/A4.0 DOOR JAMB OF NEW STOREFRONT. PROVIDE
 COMPLETE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS.
 SPECIFY BUCK SIZE AND FASTENER TYPE AND SPACING. SEC.
 1609.1 FBC.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) NEW STORE FRONT DOORS.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 16 VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS
 TO BE LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON
 PLANS. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE AS REQUIRED OR PROVIDE COPIES OF
 SIGNED CONTRACTS FOR BUILDING OFFICIAL APPROVAL.
  
 17- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  