Plan Review Notes
Plan Review Notes For Permit 18120645
Permit Number 18120645
Review Stop M
Sequence Number 2
Notes
Date Text
2019-02-22 08:21:14MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MECHANICAL PLAN.
 2. DEMONSTRATE HOW THE NEW HABITABLE SPACE SHALL BE
 HEATED PER FBC R303.10.
  
 R303.10 REQUIRED HEATING.
  
 DESIGN TEMP. WEST PALM BEACH FLORIDA ? 45 DEGREES -
 WINTER
  
 FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION
 R303.10 REQUIRED HEATING. WHERE THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF
 NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
 TABLE R301.2 (1), WINTER DESIGN TEMP. (E) ?THE OUTDOOR
 DESIGN DRY-BULB TEMPERATURE SHALL BE SELECTED FROM THE
 COLUMNS OF 971/2 PERCENT VALUES FOR WINTER??.
  
 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS,
 SECTION 1101.1 SCOPE. ?AN ADDITION TO A BUILDING OR
 STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODE
 AS ADOPTED FOR NEW CONSTRUCTION??
  
 SECTION 1106 ENERGY CONSERVATION, 1106.1 MINIMUM
 REQUIREMENTS. ADDITIONS TO EXISTING BUILDINGS OR
 STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, ENERGY.
  
 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS,
 SECTION R502 ADDITIONS, ?ADDITIONS TO AN EXISTING
 BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL
 CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE
 PROVISIONS RELATE TO NEW CONSTRUCTION??.
 SECTION R502.1.1.2 HEATING AND COOLING SYSTEMS. NEW
 HEATING, COOLING AND DUCT SYSTEMS THAT ARE PART OF THE
 ADDITION SHALL COMPLY WITH SECTIONS R403.1, R403.2,
 R403.3, R403.5 AND R403.6.
  
 FBC PLUMBING, APPENDIX D, DEGREE DAY AND DESIGN
 TEMPERATURES, TABLE D101, DESIGN TEMPERATURE, WINTER,
 97 ?% = 45 DEGREES DESIGN TEMP.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  