2019-02-22 08:21:14 | MECHANICAL PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 2ND REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE MECHANICAL PLAN. |
| 2. DEMONSTRATE HOW THE NEW HABITABLE SPACE SHALL BE |
| HEATED PER FBC R303.10. |
| |
| R303.10 REQUIRED HEATING. |
| |
| DESIGN TEMP. WEST PALM BEACH FLORIDA ? 45 DEGREES - |
| WINTER |
| |
| FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION |
| R303.10 REQUIRED HEATING. WHERE THE WINTER DESIGN |
| TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C), |
| EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING |
| FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF |
| NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM) |
| ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS |
| IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE |
| INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS |
| SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS |
| SECTION. |
| |
| TABLE R301.2 (1), WINTER DESIGN TEMP. (E) ?THE OUTDOOR |
| DESIGN DRY-BULB TEMPERATURE SHALL BE SELECTED FROM THE |
| COLUMNS OF 971/2 PERCENT VALUES FOR WINTER??. |
| |
| 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS, |
| SECTION 1101.1 SCOPE. ?AN ADDITION TO A BUILDING OR |
| STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODE |
| AS ADOPTED FOR NEW CONSTRUCTION?? |
| |
| SECTION 1106 ENERGY CONSERVATION, 1106.1 MINIMUM |
| REQUIREMENTS. ADDITIONS TO EXISTING BUILDINGS OR |
| STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, ENERGY. |
| |
| 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS, |
| SECTION R502 ADDITIONS, ?ADDITIONS TO AN EXISTING |
| BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL |
| CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE |
| PROVISIONS RELATE TO NEW CONSTRUCTION??. |
| SECTION R502.1.1.2 HEATING AND COOLING SYSTEMS. NEW |
| HEATING, COOLING AND DUCT SYSTEMS THAT ARE PART OF THE |
| ADDITION SHALL COMPLY WITH SECTIONS R403.1, R403.2, |
| R403.3, R403.5 AND R403.6. |
| |
| FBC PLUMBING, APPENDIX D, DEGREE DAY AND DESIGN |
| TEMPERATURES, TABLE D101, DESIGN TEMPERATURE, WINTER, |
| 97 ?% = 45 DEGREES DESIGN TEMP. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |