2019-01-03 07:06:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NO ELECTRICAL PLAN PROVIDED FOR REVIEW. PROVIDE |
| ELECTRICAL PLAN FOR REVIEW SHOWING LOCATION OF |
| STRUCTURE OF WHERE SHUTTERS ARE TO BE INSTALLED, SIGNED |
| AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED |
| BY THE ELECTRICAL CONTRACTOR QUALIFIER. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5 |
| |
| 2. PROVIDE UL OR OTHER NRTL LISTING FOR PRODUCT |
| APPROVAL OF SHUTTERS. FBC 107.2.1 NEC 90.7, 110.2, |
| 110.3B. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |