Plan Review Notes
Plan Review Notes For Permit 18120618
Permit Number 18120618
Review Stop E
Sequence Number 1
Notes
Date Text
2019-01-03 07:06:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL PLAN PROVIDED FOR REVIEW. PROVIDE
 ELECTRICAL PLAN FOR REVIEW SHOWING LOCATION OF
 STRUCTURE OF WHERE SHUTTERS ARE TO BE INSTALLED, SIGNED
 AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED
 BY THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. PROVIDE UL OR OTHER NRTL LISTING FOR PRODUCT
 APPROVAL OF SHUTTERS. FBC 107.2.1 NEC 90.7, 110.2,
 110.3B.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved