2018-12-26 06:42:39 | 1) YOU HAVE SUBMITTED A TABLE FOR THE 10 PSI SYSTEM BUT |
| NOT FOR THE LOW PRESSURE SYSTEM. SUBMIT TWO COPIES OF |
| THE APPLICABLE SIZING TABLES USED TO SIZE THE GAS |
| SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING |
| WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER |
| STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4, |
| 401.8, 402.3, AND TABLES 402.4 (1) THRU 402.4 (37) OR |
| 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2, |
| & G2413.3. |
| 2) THERE ARE EXISTING GAS APPLIANCES ON THIS SYSTEM.THE |
| PLANS INDICATE AND CITY RECORDS SHOW AN EXISTING GAS |
| SYSTEM FOR THIS ADDRESS. THE BTU LOAD OF THE EXISTING |
| GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE |
| SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. |
| IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. |
| |
| NOTE: I AHVE INCLUDED A COPY OF THE ORIGINAL GAS PLAN |
| IN THE PERMIT APPLICATION PACKAGE THAT CAN BE USED AS A |
| REFERENCE ONLY. IT IS NOT TO BE USED FOR PERMITTING. |
| |