2019-01-04 06:48:46 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION AND PANEL |
| SCHEDULE. PANEL SCHEDULE ISN'T LABELED CORRECTLY AND |
| THERE WAS NO CLEAR LOAD CALCULATION PROVIDED. FBC |
| 107.2.1 NEC 220, FBC RE E3602.2 NEC 210.8, 210.12, |
| 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| |
| 2. MINIMUM OF 2 SMALL APPLIANCE BRANCH CIRCUITS |
| REQUIRED IN KITCHEN. NEC 210.11C1 |
| |
| 3, FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| |
| 4. PROVIDE SPEC SHEET FOR WASHER/DRYER. 1, 2-POLE 30AMP |
| BRANCH CIRCUIT DOESN'T SEEM FEASIBLE TO SUPPLY BOTH |
| APPLIANCES. FBC 107.2.1 NEC 110.3B |
| |
| 5. WRONG BRANCH CIRCUIT CONDUCTOR SIZE AND OVERCURRENT |
| PROTECTION SIZE FOR A 7KW WATER HEATER. PROVIDE |
| CORRECTION. NEC 422.10, 422.11E, 422.13 |
| |
| 6. BONDING BRIDGE REQUIRED AT SERVICE NEC 250.94. |
| |
| 7. MINUMIM OF 2 GROUND RODS REQUIRED FOR GROUNDING |
| ELECTRODE SYSTEM NEC 250.53A2 |
| |
| 8. RAISE VALUE. $5000 VALUE FOR A ENITRE HOUSE REMODEL |
| AND SERVICE UPGRADE IS LOW. IF ACCURATE VALUE ISN'T |
| GIVEN VALUE WILL BE SET BY BUILDING OFFICIAL. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |